1. General Scope
EMT CO., LTD. Pole Top Auto-RECLOSER is installed for Automatic tripping as equipped IDMT curve with Polymer , Solid Insulated RECLOSER of installation on Distribution Pole.
AUTO RECLOSER shall be able to automatically trip on Overload Phase Fault Trip, and Ground Fault , Sensitive Earthing Fault, and RECLOSER can automatically reclose with Reclosing controller as programmed sequence to minimize SAIDI, SAIFI.
2. Auto Recloser Function
2.1 Automatic Fault Trip as Circuit Breaker with IDMT Curve
2.2 Automatic Reclosing as Programmed sequence
2.3 Available of SCADA system with RTU (or, Integrated RTU)
3. Automatic Trip & Reclosing Function
3.1 RECLOSER shall make Trip as IDMT Curve (IEC Class A curve ( Standard Inverse )
* Very Inverse (VI), Extremely Inverse (EI), Other T-C Curve is available optionally.
3.2 RECLOSER shall close automatically as programmed reclosing sequence.
3.3 Automatic Reclosing Counts and Time Interval are programmable as User's application.
3.4 No reclosing function shall make only one time trip
4. General Specification
4.1 Rating Voltage and Current : 36kV,
4.2 Rating Current : 630 A
4.3 Insulation Media : Polymer ( Solid Insulation Material )
4.4 Arch extinguishing Method
o Vacuum Interrupter : 12 ~ 35 kV, 400, 630 (800) A
4.5 Fault Current Interrupting Capability ; 12.5 kA (25kA)
4.6 Short Time Withstand Current : 12.5 kA (1 sec.), [25kA, 3 sec.]