45KW  biogas  generating  set
 
Genset  working  condition:
  Acceptable  working  conditions:
Ambient  temperature  :  0° C~+40° C 
(antifreeze,   oil  and  water  heater  needed  for  below  0° C)
Relative  humidity: lower  90%(20° C)
Altitude: lower  than  500m
 
Normal  working  conditions:
Genset  can  run  at  rated  power  on  the  conditions:
Atmospheric  Pressure:   100kPa,   Ambient  Temp:   20° C,  Relative  Humidity
 
Applied  gas:
Biogas
 
Gas  genset  data
Genset  model
KDGH45-GZ
Prime  power  (kW/KVA)
45/56.25
Continuous  Power  (KW/KVA)
40/50
Output  Voltage  (V)
400V,   3  Phases  4  Lines 
Power  factor 
0.8  lagging
Frequency  (Hz)
50
Rated  speed  (RPM)
1500
Open  type  Genset 
Overall  Dimension  (mm)
2300x900x1400
Soundproof  type 
Genset  Dimension  (mm) 
2900x1200x1800
Net  weight  without  canopy(kg)
1400
Gas  Engine  Data
Model
HG6B
Brand
CAMDA
Type
4  stroke,   water-cooling,   dry  cylinder  liner,   electronic  control 
ignition  system,   pre-mixed  perfect  mixed  burning
Cylinders&   Arrangement
6L
BoreXStroke(mm)
102X120
Displacement(L)
5.88
Compression  ratio
11.5:1
Aspiration
Natural
Cooling  Method
Radiator  fan  water  cooling
Governor  type
(speed  regulating  type)
Electronic  governing
Starting  method
Electric,   24  V  motor 
The  lowest 
gas  consumption(m3/kw. h)
0.6
Idling  speed(r/min)
700
Oil  recommended
SAE  15W-40  CF4  or  above
Oil  consumption
≤ 1.0g/kW. h
Alternator  Data
Brand
France  Leroy  Somer 
Model
LSA43.2M45/48KW
Rated  power
48kW  /  3  phase
Rated  Voltage  (V):
380~480  (± 0.5%)(AC)
Type
3  phase/4  wire,   brushless,   automatic  voltageregulator,   drip  proof,
protected  type.
Frequency  (Hz)
50
Efficiency:
89.9%
Voltage  regulation
±   0.5  %(adjustable)
Insulation  class:
Class  H
Protection  class:
IP  23
cooling  method:
wind-cooling,   self-heat-rejection
Voltage  regulating  mode
Automatic  voltage  regulator
Compliant  with 
international  standards:
IEC  60034-1,   NEMA  MG1.22,   ISO  8528/3,  
CSA,   UL  1446,   UL  1004B  on  request,   marine  regulations,   etc