Product Main

Specifications

80KW biogas generator set
Gas Genset working condition:
Acceptable working conditions:
Ambient temperature : 0°C~+40°C 
(antifreeze, oil and water heater needed for below 0°C)
Relative humidity:lower 90%(20°C)
Altitude:lower than 500m
 
Normal working conditions:
Genset can run at rated power on the conditions:
Atmospheric Pressure: 100kPa, Ambient Temp: 20°C, Relative Humidity: 30%
 
Applied gas:
Biogas
 
Gas genset data
Genset model
KDGH80-GZ
Prime power/Continuous Power(kW/KVA)
80/100
Output Voltage (V)
400V, 3 Phases 4 Lines 
Power factor 
0.8 lagging
Frequency (Hz)
50
Rated speed (RPM)
1500
Open type Genset Overall Dimension (mm)
3000x1100x1800
Soundproof type Genset Dimension (mm) 
4600x1600x2200
Net weight without canopy(kg)
2500
Gas Engine Data
Model
HGN14
Brand
CAMDA
Type
4 stroke, water-cooling, 
wet cylinder liner, electronic-control
ignition system, pre-mixed 
perfect mixed burning
Cylinders& Arrangement
6L
BoreXStroke(mm)
140X152
Displacement(L)
14
Compression ratio
11.5:1
Aspiration
Natural
Cooling Method
Radiator fan water cooling
Governor type(speed regulating type)
Electronic governing
Starting method
Electric, 24 V motor 
The lowest gas consumption(m3/kw.h)
0.6
Idling speed(r/min)
700
Oil recommended
SAE 15W-40 CF4 or above
Oil consumption
≤1.0g/kW.h
Alternator Data
Brand
France Leroy Somer 
Model
LSA44.2VS45/84KW
Rated power
84kW / 3 phase
Rated Voltage (V):
380~480 (±0.5%)(AC)
Type
3 phase/4 wire, brushless, 
automatic voltage 
regulator, drip proof, protected type.
Frequency (Hz)
50
Efficiency:
91.2%
Voltage regulation
± 0.5 %(adjustable)
Insulation class:
Class H
Protection class:
IP 23
cooling method:
wind-cooling, self-heat-rejection
Voltage regulating mode
Automatic voltage regulator
Compliant with international standards:
IEC 60034-1, NEMA MG1.22, ISO 8528/3, CSA, UL 1446, 
UL 1004B on re