Product Main

Specifications

 

High frewuency and online double conversion      
Wide input voltage and frequency        
Self-diagnosis system at ups start        
Digital control technoloy and advanced PFC      
Short and overload protection        
Output PF0.8/0.9(optional)        
Lighting and surge protection 1050j      
Cold start             
Smart RS232(USB, SNMP OPTIONAL)        
Battery quantity flexiable        
EMI/RFI noise filter          
Overview
With true double-conversion design, PowerMaster series provides powerful and overall protection to your sensitive devices. It can accept wider input voltage for harsh environment. It's perfect protection for your precisous servers and workstaiosn. 
Specifications          
Model PM1000S PM1000L PM2000S PM2000L  PM3000S PM3000L 
Capacity 1KVA/0.8kW 1KVA/0.8kW 2KVA/1.6kW 2KVA/1.6kW 3KVA/2.4kW 3KVA/2.4kW
Phase Single
Rectifier input
Input power factor above 0.98
Input distortion less than 5%
Rated voltage 110v/120v/127v
Input voltage range 60-140v
 
Rated frequency 50/60hz(auto sensing)
Input frequency range 40-70hz
By-pass input
Input voltage range 60VAC—140VAC
Frequency following range minus/plus5%
Recharge battery
Floating charge voltage 27/41VDC 27/41VDC 55/82/110VDC 55/82/110VDC 82/110VDC 82/110VDC
Recharging current 1A(inbuilt battery) 8A 1A(inbuilt battery) 8A 1A(inbuilt battery) 8A
Battery
Battery quantity 24/36VDC 48V/72/96VDC 72/96VDC
AC output
Power factor 0.8
Phase single
Rated voltage 110v/120v/1270v+/-1.5%
Frequency 50/60hz(auto sensing)
Frequency stability ±0.1HZ(battery inverter)
Voltage stability within±1.5%( Static)
  Crest factor 3:1(max)
Wave distortion Linear load less 3%, Non-linear load less 5%;
Over load ability 30s when overload is 108%~150%;200ms above 150%;
Transfer time 0s
Alarm
AC abnomal Alarm every 4 seconds
Battery low voltage Keep alarm every 1 second
Overload Keep alarm every 0.5 second
Failure Keep alarm
System
Efficiency above 87%
Display LCD+LED
Protection Output short circuit , Overload , Output low voltage, Battery low voltage,                  Over-temperature etc.
 added over-voltage protection and over-tempreture protection to charger PCB, and added soft-start function for each function module
Infterface RS232(USB OPTIONAL)
Working Temp. 0~40℃
Relative humidity 0~90%( No coagulation)
Cooling Intelligent speed-control Fan
Input & output  Socket(Optional)
Others
Surge protection IEC60664—1 Graded protection
EMI EN 55022  Grade A
ESD IEC 1000-4-2:Grade 3
EFT IEC 1000-4-4:Grade 3
RS IEC 1000-4-3:Grade 3
SURGE IEC 1000-4-5:Grade 3
Physical
Weight(N/G)kgs 7.0/8.0 12/13.5 17.0/18.0 32.0/33.0 17.0/18.0 32.0/33.0
Unit Size 144* 418 * 215mm 191 * 331*474mm *