single phase online low frequency UPS industrial uninterrupted Power Supply SU1K~SU20K
<
<
| SU1K~SU20K (Single in and Single out) | ||||||||
| Mode | SU1K | SU2K | SU3K | SU6K | SU10K | SU15K | SU20K | |
| Capacity (VA/W) | 1K/0.8K | 2K/1.6K | 3K/2.4K | 6K/4.8K | 10K/8K | 15K/12K | 20K/16K | |
| Input Voltage | Single phasewith two lines + ground wire, 220V±25% | |||||||
| Battery Voltage | 48V/96V | 96V/192V | 192V | |||||
| Noise | ≤52dB (Distance 1m) | ≤60dB (Distance 1m) | ||||||
| Size (WxDxHmm) | 530 x 264 x 592 | 630 x 343 x725 | ||||||
| Weight (KG) (excluding the battery) | 30 | 40 | 45 | 60 | 100 | 125 | 150 | |
| Input | Frequency | 50Hz/60Hz ±10% | ||||||
| Power Factor | ≥0.95 | |||||||
| Output | Voltage | 220V±0.5% | ||||||
| Voltage Regulation | Stable voltage ±1%, Dynamic voltage ±2%, (0-100% load fluctuation <20ms) | |||||||
| Frequency Stableness | 50Hz/60Hz ± 0.05% (DC supply) | |||||||
| Frequency Torsion Rate | Less than 1Hz/second | |||||||
| Instant Load Status | ±0.4% (100% instant load fluctuation) | |||||||
| Harmonic Distortion | For linear load, less than 3%(full load), Total rectifying, harmonics is less than 5% | |||||||
| Overload Capacitance | 1.5 | |||||||
| Wave Form | Sine Wave | |||||||
| Efficiency | Input AC to Output AC | ≥95% | ||||||
| Transfer Time | Mains power supply Fails or Restores | 0 second | ||||||
| Turns from UPS to Bypass | less than 4ms | |||||||
| Battery | Battery Type | Lead-acid sealed, maintenance-free | ||||||
| Charging Time | After it is fully charged, it can be filled to 90% of the total capacity after it is charged for 8 hours | |||||||
| Warning Sound | Battery Discharge | If the electric supply fault, it buzzes once every 4 seconds | ||||||
| If the battery is low, it buzzes once every 1 second | ||||||||
| If the battery stops discharging, it buzzes continuously | ||||||||
| Fault Abnormal | Buzzes continuously | |||||||
| Protecting Device | Battery | Automatically shuts down the machine when the battery power is low, it has no fuse switch protection | ||||||
| Overload | After the overload (110~150%) lasts for 30 seconds, t automatically jumps to bypass. It can automatically restore normal state | |||||||
| Over Temperature | If the internal temperature of the UPS >85℃, it will automaticall jump to bypass | |||||||
| Output Short Circuit | Limits Current, Automatically shuts down the machine, without fuse switch protection | |||||||
| US Abnormal | Automatically jumps to bypass mode and starts direct mains power supply | |||||||
| Noise Filter | 10~10KHz at 40db, 100KHz~100MHz at 70db | |||||||
| LCD Panel Board | LCD Display | With display input voltage, output voltage, frequency, Dc voltage, Output power efficiency (%) | ||||||
| Battery Low Voltage | One LED, It glows when the battery voltage is now | |||||||
| Outside Environment | Temperature | (-10℃)~ (+50℃) | ||||||
| Relative Humidity | 0~93%, no condensation | |||||||
| Operation Condition | ≤3000m | |||||||