CE certificated,LVD&EMC passed
low than 0.6g vibration
High power transfer 98%
multiple signal input and output
RS485 modbus
GK600 Technical specifications
low than 0.6g vibration
High power transfer 98%
multiple signal input and output
RS485 modbus
GK600 Technical specifications
Power input
|
Rated voltage
|
3-phase AC380V/AC400V/AC415V/AC440V/AC460V/AC480V
|
|
Frequency
|
50Hz/60Hz, fluctuation range ±5%
|
||
Allowable range of voltage
|
Continuous voltage fluctuation ±10%, short fluctuation -15%~+10%, i.e. 323V~528V;
Voltage out-of-balance rate <3%, distortion rate as per the requirements of IEC61800-2
|
||
Output voltage (V)
|
3-phase: 0~ rated input voltage, error < ±3%
|
||
Output frequency (Hz)
|
0.00~ 600.00Hz; unit: 0.01Hz
|
||
Overload capacity
|
150% - 1min; 180% - 10s; 200% - 0.5s
|
||
Operational control characteristics
|
Control mode
|
V/f control
Vector control without PG 1
Vector control without PG 2
|
|
Range of speed regulation
|
1:100 ( V/f control, vector control without PG 1)
1:200 (vector control without PG 2)
|
||
Velocity control accuracy
|
±0.5% (V/f control)
±0.2% (vector control without PG 1 & 2)
|
||
Velocity fluctuation
|
±0.3% (vector control without PG 1 & 2)
|
||
Torque response
|
< 10ms (vector control without PG 1 & 2)
|
||
Starting torque
|
0.5Hz: 180% (V/f control, vector control without PG 1)
0.25Hz: 180% (vector control without PG 2)
|
||
Basic functions
|
Start frequency
|
0.00~ 600.00Hz
|
|
Acceleration/deceleration time
|
0.00~60000s
|
||
Carrier frequency
|
0.7kHz~16kHz
|
||
Frequency setting mode
|
Digital setting + operating panel ∧/∨
Digital setting + terminal UP/DOWN
Communication setting
Analog setting (AI1/AI2/EAI)
Terminal pulse setting
|
||
Starting method
|
Start from starting frequency
DC braking and then starting
Velocity search based starting
|
||
Stopping method
|
Stop by deceleration
Free stop
Stop by deceleration + DC braking
|
||
Basic functions
|
Dynamic braking capacity
|
Brake unit action voltage: 650V~750V; service time: 0.0~100.0s; brake unit for GK600-4T45G/55L or below could be internally mounted
|
|
DC braking capacity
|
DC braking start frequency: 0.00~600.00Hz
DC braking current: 0.0~100.0%
DC braking time: 0.0~30.00s
|
||
Input terminals
|
Six switching quantity input terminals (expandable up to seven), one of which could be used for high-speed pulse input. Compatible with active open collectors NPN, PNP and dry contact input
Two analog quantity input terminals, of which one is for voltage/current input, and the other for voltage input (expandable up to three; extension terminal is for voltage/current input)
|
||
Output terminal
|
One high-speed pulse output terminal, 0~50kHz square wave signal output; output of physical quantities such as set frequency and output frequency is available
One switching quantity output terminal
A group of relay output terminals (expandable up to two groups)
|
||
One analog quantity output terminal (extendable up to two), voltage/current output optional; output of physical quantities such as set frequency and output frequency is available
|
|||
Featured functions
|
Parameter copy, parameter backup, common DC bus, free switching between two groups of motor parameters, flexible function code display & hiding property, various main & auxiliary settings and switchover, a variety of acceleration/deceleration curves options, automatic correction of analog quantity, contracting brake control, up to 16-speed operation (2-speed supports flexible frequency setting mode), wobbling frequency control operation, fixed-length control, counting function, three-group failure logging, over excitation braking, overvoltage stall, under voltage stall, restart upon power down, hopping frequency, frequency binding, free switching between four sections of acceleration/deceleration time, motor temperature protection, flexible fan control, process PID control, simple PLC, flexible multi-functional key setting, droop control, parameter identification, field-weakening control, high-precision torque limitation, V/f separation control
|
||
Protection function
|
Refer to Chapter VII - Fault Diagnosis and Exception Handling
|
||
Environment
|
Place of operation
|
Indoors, without direct exposure to sunlight, free of dust, corrosive gases, flammable gases, oil mist, water vapor, water drip or salt content etc.
|
|
Height above sea level
|
0~2000m
Derating is required where height above sea level is more than 1,000m; each increase of 100m in height corresponds to a decrease in rated output current by 1%
|
||
Ambient temperature
|
-10℃~50℃
|
||
Humidity
|
5~95%, condensation not allowable
|
||
Vibration
|
Less than 5.9m/s2 (0.6g)
|
||
Storage temperature
|
-40℃~+70℃
|
||
Others
|
Efficiency
|
Rated power
7.5kW and below: ≥93%
11~ 45kW: ≥ 95% 55kW and higher: ≥98%
|
|
Installation mode
|
Wall-mounted
|
||
Protection level
|
IP20
|
||
Cooling
|
Air Cooling
|
||