Product Main

Quick Details

Rated Current: 1440A
Rated Voltage: 440V
Rated Power: 800KW
Frequency: 60HZ
Speed: 1800RPM
Output Type: AC Three Phase
Model Number: JGC800GF
Brand Name: FD
Place of Origin: China (Mainland)
Engine Model: KTA38-G2A
Configuration: 4 cycle , 12 cylinders in "V"
Aspiration: Turbocharged after water-cooled
Bore*Stroke: 159 *159mm
Prime Power: 915KW
Cooling System: Water-cooled
Alternator model: MX-800-4
Exciter type: Single bearing, Brushless, Self-excited

Specifications

 


60HZ Cummins Genset KTA38-G2A for Sale
 

General feature

●   All qualified generator sets are subjected to a comprehensive performance test which includes 50% load, 75% load, 100% load, 110% load and to check, verify that all control systems, alarm and shut-down protection.

●    Equipped with battery charger and 24V high performance maintenance-free lead-acid starting batteries and connecting cables.

●   Equipped with industrial silencer and flexible exhaust hose.

●   Equipped with 8-hours operation base fuel tank.

●   Equipped with PEOPLE MCCB circuit breaker.

●   Designed to Comply with ISO8528/GB2820.

●   Powered by Cummins engine and coupled with Marathon alternator.
 

Advantages

● Stability, reliability and easy-service

● Low operating and maintenance cost

● Widely used, location to meet customer needs

● Easy-installation, easy-operation and maintenance
 

Genset Technical Data

Prime power

800 kW

Standby power

880kW

Rated speed

1800 RPM

Output frequency

60 Hz

Phase

3

Rated voltage                 

440 V

Engine model

KTA38-G2A

Alternator model

MX-800-4

Prime Power : Prime power is available for an unlimited number of annual hours in variable load application, in accordance with GB/T2820-97; A 10% overload capability is available for a period of 1 hour within a 12-hour period of operation.

Standby Power Rating : The standby power rating is applicable for supplying emergency power for the duration of a utility power interruption. No overload, utility parallel or negotiated outage operation capability is available at this rating.

Reliable Performance

Voltage regulation

Voltage regulation maintained within ±0.5% as follow:

●Power factor Between 0.81.0 lag

●From no load to full load, any steady load

●Speed droop variation under 4.5%

Frequency/Speed undulation

●Change load from 0-100%, Frequency/Speed Droop Ratio within 5%

●Load from 25-100%, any steady load Frequency/Speed undulation within 0.25%

Effect factor of telecom

●Telephone Influence Factor (TIF) : Less than 50

                           THF : Less than 2%

Certification

●ISO8528, GB/T2820

●EN12601:2001, EN60034-22:1997, EN60204-1:2006

●ISO9001:2008 Quality Control System

●CE

Open Type

Overall size (L*W*H)

4500*2060*2430

Weight: 6900kg

For reference only

ENGINE SPECIFICATION

Cummins Diesel Engine Technical Data

Engine Model

KTA38-G2A

Configuration

4 cycle , 12 cylinders in "V"

Aspiration

Turbocharged after water-cooled

Bore×Stroke

159 x159mm

Rated speed

1800rpm

Displacement (Liter)

38.0L

Compression Ratio

14.5:1

Prime Power

915KW

Speed Governor

electrical

Cooling System

Water-cooled

Speed Stability (%)

≤5%

Fuel Consumption at 100% Load

209g/kw.h

Starter Motor

DC24V,

Alternator SPECIFICATION

Marathon Alternator Technical Data
  

Alternator model

MX-800-4

Alternator manufacturer

Marathon

Exciter type

Single bearing, Brushless, Self-excited

Rated output prime power

800 kW

Rated speed

1800 RPM

Rated frequency

60 Hz

Phase

3

Rated voltage

440V

Power factor

0.8

Voltage adjust range

≥5%

Voltage regulation NL-FL

≤±1%

Insulation grade

H

Protection grade

IP23


Control System

Control System HGM6110

All FENGDE gensets have a control cubicle (the smart gen HGM6110 as standard) mounted on a isolated support, which has the following features.

Electronic digital control module with monitoring/control facility and warning indicators

Automatic shutdown protection

Emergency stop button (lock-down type)

AC output circuit breaker with over-current protection

DC circuit control switch

The control module display

Generator voltage

Generator voltage

Output frequency

Engine speed

Battery voltage

Engine run-time (Hours)

Note:

1. The engine coolant temperature displayed by water temperature gauge

2. The engine oil pressure displayed by oil pressure meter

3. Generator current displayed by current meter, to change switch for each phase displayed separately

The control module display for failure information

Overspeed / underspeed

Emergency stop

Low oil pressure

High water temperature

Failure to start

Battery charger failure

Automatic shutdown

Low engine oil pressure

High engine water temperature

Overspeed/underspeed

Failure to start after three attempts

The control modules option

DSE7220, HGM6520, HGM6120, DSE7210

Remarks: For the specific and detailed features of the above types, please refer to " Control System Selection" file.

Warranty

All Fengde goods are warranted in accordance with our warranty terms for a period of 12 months from date of dispatch.