Rated Current: | 180A |
---|---|
Rated Voltage: | 400V |
Rated Power: | 100KW |
Frequency: | 50HZ |
Speed: | 1500RPM |
Output Type: | AC Three Phase |
Model Number: | JGC100GF |
Brand Name: | FD |
Place of Origin: | China (Mainland) |
Engine Model: | 6BTA5.9-G2 |
Aspiration: | Turbocharged after water-cooled |
Bore*Stroke: | 102 *120 mm |
Speed Governor: | electrical |
Alternator Model: | MP-104-4 |
Exciter type: | Brushless, Self-excited |
Quick Details
Specifications
100KW Trailer Diesel Generator
STANDARD SPECIFICATION
● Coupled with Cummins diesel engine and Stamford
Or Marathon alternator
● 24V DC start motor and storage battery
● Brushless, Self-excited, IP23, insulation class H alternator
● 40℃ radiator as standard, 50℃ is optional
● Key start panel control system as standard, digital auto-start panel is optional
● Optional open type or silent type
● All generator sets are gone through rigorous testing before being released to the market place, including 50% load, 75% load, 100% load , 110% load and all protection function (overspeed stop, high water temperature, low oil pressure, battery charging fail, emergency stop)
General feature
Genset Main Technical Data
Generator Model |
JGC100GF |
Output power |
100KW |
Voltage |
380V/220V |
Frequency |
50HZ/1500 rpm |
Power factor |
0.8(lag) |
Governor type |
Electric |
Reliable Performance
Voltage regulation
Voltage regulation maintained within ±0.5% as follow:
● Power factor Between 0.8~1.0 lag
● From no load to full load, any steady load
● Speed droop variation under 4.5%
Frequency/Speed undulation
● Change load from 0-100%, Frequency/Speed Droop Ratio within 5%
● Load from 25-100%, any steady load Frequency/Speed undulation within 0.25%
Effect factor of telecom
● Telephone Influence Factor (TIF) : Less than 50
THF : Less than 2%
Certificate
● ISO8528, GB/T2820
● EN12601:2001, EN60034-22:1997, EN60204-1:2006
●
ISO9001:2008 Quality Control System
Dimension and Weight
Open Type
Overall size (L*W*H)
2150*750*1200
Weight: 1050kg
ENGINE SPECIFICATION
Cummins Diesel Engine
Technical Data
Engine Model |
6BTA5.9-G2 |
Configuration |
4 cycle , 6 cylinders in line |
Aspiration |
Turbocharged after water-cooled |
Bore×Stroke |
102 x120 mm |
Rated speed |
1500rpm |
Displacement |
5.9 L |
Compression Ratio |
17.5:1 |
Prime Power |
100KW |
Speed Governor |
electrical |
Cooling System |
Water-cooled , 40℃ Radiator As Standard, 50℃ Is Optional. |
Speed Stability (%) |
≤5% |
Fuel Consumption at 100% Load |
211g/kw.h |
Starter Motor |
DC24V, |
Alternator Specification
Technical Data
Brand |
MARATHON |
Alternator Model |
MP-104-4 |
Capacity |
104KW |
Voltage |
220/380V |
Frequency & Speed |
50HZ/1500RPM |
Exciter type |
Brushless, Self-excited |
Power factor |
0.8 |
Voltage Adjust range |
≥5% |
Voltage Regulation NL-FL |
≤±0.5% |
Insulation Grade |
H |
Protection Grade |
IP23 |
Control System
1. Standard: HGM180HC Key Start
Providing the standard functions as follows:
(Also can be made according to the customers' special requirements)
*Start/Stop controller
*Ampere meter
*Voltmeter and selector switch
*Frequency meter/ Water temperature gauge/ Oil pressure gauge/ Hour counter/ Battery voltage meter
*Emergency stop pushbutton
*Alarm System: Over speed, High Engine Temperature
Low Oil Pressure, Charge Fail
*Protection System: Over speed, High Engine Temperature, Low Oil Pressure, Emergency Stop. And the other protection function pre-setting
2. Option: Smartgen HGM6110 Digital Auto Start
3. Option: Smartgen HGM6120 Digital Auto Start
(Option assembled with the ATS)
4. Option: Deep Sea DSE5210 Digital Auto Start
5. Option: Deep Sea DSE5220 Digital Auto Start
(Option assembled with the ATS)
Digital Auto-start Generator controller integrating digital, intelligent and network techniques is used for automatic control system of diesel generator. It can carry out functions including automatic start/stop, data measure and alarming. Optionally assembled with the ATS, it can carry out auto-switching between the outer power and generating setpower. (AMF)
Functions:
*Automatic Start/Stop
*3 start attempts failure and Automatic Crank Disconnect
*Parameters display (V/A/Hz/Hour)
*Engine monitoring and protection
*Charge alternator exciting and Charge alternator fail alarm
*Running hour countin
*Settings can be adjustable via key buttons on front panel