Rated Voltage: | 230V/400V |
---|---|
Rated Power: | 7KW/9KVA |
Frequency: | 50Hz |
Speed: | 1500rpm |
Output Type: | AC Three Phase |
Model Number: | AP10-I |
Brand Name: | AOSIF |
Place of Origin: | China (Mainland) |
Quick Details
Specifications
Manufacturer |
Perkins Engines Company Limited |
Model |
403A-11G1 |
Engine Speed |
1500rpm |
Engine Standby Power (LTP) –KW |
9.5 |
Engine Prime Power (PRP) –KW |
8.6 |
Type |
4 stroke cycle , Non direct injection, 3 cylinder
|
Aspiration Type |
Naturally aspirated
|
Bore mm/Stroke mm |
77/81 |
Displacement |
1.131L |
Compression Ratio |
23:1 |
Fuel Consumption |
Load |
Fuel Consumption --g/kWh |
Fuel Consumption - L/h |
Engine Output at generator set Standby output |
268 |
3.6 |
Engine Output at generator set prime output |
248 |
3 |
Fuel Consumption at 75% of generator set prime output |
257 |
2.3 |
Fuel Consumption at 50% of generator set prime output |
280 |
1.7 |
Exhaust System
Maximum allowable exhaust back pressure - kPa |
10.2 |
Max. Exhaust Temperature(Before Turbo)-℃ |
368 |
Exhaust Gas Flow - m3/min |
1.66 |
Intake System
Dirty filter air filter maximum inlet resistance -kPa |
6.4 |
Clean filter air filter maximum inlet resistance - kPa |
3 |
Lubrication System
Minimum oil pressure - kPa |
120 |
Safety valve opening pressure -kPa |
304-500 |
Allowable maximum oil temperature - ℃ |
125 |
System total capacity -L |
4.9 |
Fuel System
Fuel system form |
Perkins non direct injection system |
Fuel pump pressure - kPa |
10 |
Fuel pump maximum flow - L/h |
63 |
Cooling System
Cooling water capacity - L |
5.2 |
The maximum static pressure of cooling water above the center line of the engine crankshaft- kPa |
30.4 |
Standard thermostat temperature adjustment range - ℃ |
75-87 |
Maximum box temperature--standby power/prime power- ℃ |
112 |
Electrical System
Recommended minimum battery capacity |
80Ah |
Starting motor -V(volt) |
12 |
Charging Alternator Capacity -A(ampere) |
15 |
Generator technical Data
|
Model |
LSA40VS1 |
Continuous/40- ℃ |
8kw |
AVR Model |
R220 |
Number of phase |
3 |
Power factor (Cos Phi) |
0.8 |
Altitude |
≤ 1000 m |
Over speed |
2250RPM |
Number of Pole |
4 |
Exciter type |
SHUNT |
Insulation class |
H |
Adjusting rate of stable voltage |
±0.5% |
Transient state voltage |
300% (3 IN) : 10s |
Wave aberration rate of votage( THD) |
no load<3%,on load<5% |
Telephone harmony wave factor of telephone TIF |
< 50 |
Bearing |
Single |
Coupling |
Direct |
Protection class |
IP23 |
Balancing |
All rotors are strictly in accordance with ISO 1940 and NFC51-111 the standard requirements for balancing. |