Electrical specification:
Conforms to standard of electrical:
EN60898(IEC898) GB10963-99
Rated current(Ue): 230V/440V; 50/60HZ
Rated breaking capacity:
10KA IEC898(0. 5~63A); 15KA IEC947-2(0. 5~63A)
Short circuit breaking capacity of DC:
Max. 48V(KL7...., 10KA)single pole
Max. 250V(KL7-DC, 6KA)single pole
Perfermance:
C, D characteristic curve
Max. Fuse that can be connected to:
100AgL(>10KA)
Selective grade:
3
Working ambient temperature:
-5 TO+40 Degree Celsius
Enclosed protective class:
P40(Under mounting)
Life: Electrical Mechnical
Not less of 8000times switching operation
Not less of 20000 times switching operation
Package:
1P 240pcs/CTN, 535*240*325mm
2P 120pcs/CTN, 535*240*325mm
3P 80pcs/CTN, 535*240*325mm
.cn