Product Main

Specifications

DPNL
Application
The products provide protection against earth leakage faults, overloads, short circuits and overvoltage in commercial and domestic installation.

 

--------------------------------------------------------------------------------

Features
The RCBO with both disconnected neutral and phase guarantees its proper actuation against earth leakage fults even when the neutral and phase are wrongly connected.
The electronic RCBO incorporate a filtering device preventing the risks of unwanted tripping due to transient voltages and transient currents.
Positive contact indication in accordance with 16th edition of the IEE wiring regulation.

--------------------------------------------------------------------------------

Technical data
Current ratings(30C): 6, 10, 16, 20, 25, 32A
Rated voltage: 230V
Breaking capacity: 3000A
Tripping characteristics: Type C (IEC898) Magnetic setting 5 to 10In
Overvoltage tripping value: 280+-5%
Sensitivity: 30mA, 100mA, 300mA
Rated non-tripping residual current: 0.51In
Connection capacity: Tunnel terminals up to 100m2
Width in 9mm modules: 4
Standard: IEC1009

--------------------------------------------------------------------------------

Installation
Distribution board and standard enclosures
On symmetrical DIN rail 35mm2
Panel mounting