Cat5e Cat 6 Cat 6A Cat 7 cable
Application: 100 Base-T4
100 Base-TX
100VG - AnyLAN
1000 Base-T (Gigabit Ethernet)
155 Mbps ATM
622 Mbps AT
Reference Standard: EIA/TIA 568B & ISO/IEC 11801
Cable Construction
Conductor: Solid Bare Copper AWG: 23
Conductor Diameter(mm): 0.574 Insulation: Solid PE
Average Thickness (mm): 0.2 Insulation Diameter(mm): 1.00
Drain wire: Tinned copper Construction (mm): 7/0.2
Al foil: Aluminium/PET fiol
Sheathing: PVC /FRPVC/LSOH
Core Identificatin/Color Code: According to customer request
Bending Radius: 6xOverall Diameter
Fire Performance
Flame propagation Test to IEC 332 Part 1(PVC)
Flame Propagation Test to IEC 60332 Part 1 and Part 3
|
Performance | ||||
|
Frequency |
RL |
Attenuation |
NEXT |
PSNEXT |
|
(MHz) |
(dB) |
(dB/100m) |
|
|
|
|
min. |
max |
min (dB) |
min (dB) |
|
1.000 |
20.00 |
2.00 |
74.30 |
72.30 |
|
4.000 |
23.00 |
3.80 |
65.30 |
63.30 |
|
8.000 |
24.50 |
5.30 |
60.80 |
58.80 |
|
10.00 |
25.00 |
6.00 |
59.30 |
57.30 |
|
16.00 |
25.00 |
7.60 |
56.20 |
54.20 |
|
20.00 |
25.00 |
8.50 |
54.80 |
52.80 |
|
25.00 |
24.30 |
9.50 |
53.30 |
51.30 |
|
31.25 |
23.60 |
10.70 |
51.90 |
49.90 |
|
62.50 |
21.50 |
15.40 |
47.40 |
45.40 |
|
100.00 |
20.10 |
19.80 |
44.30 |
42.30 |
|
200.00 |
18.00 |
29.00 |
39.80 |
37.80 |
|
250.00 |
17.30 |
32.80 |
38.30 |
36.30 |
|
Frequency |
ELFEXT |
PSELFEXT |
|
ACR |
|
(MHz) |
|
|
|
|
|
|
min (dB) |
min (dB) |
|
|
|
1.000 |
67.80 |
64.80 |
|
72.30 |
|
4.000 |
55.80 |
52.80 |
|
61.50 |
|
8.000 |
49.70 |
46.70 |
|
55.50 |
|
10.00 |
47.80 |
44.80 |
|
53.30 |
|
16.00 |
43.70 |
40.70 |
|
48.60 |
|
20.00 |
41.80 |
38.80 |
|
46.30 |
|
25.00 |
39.80 |
36.80 |
|
43.80 |
|
31.25 |
37.90 |
34.90 |
|
41.20 |
|
62.50 |
31.90 |
28.90 |
|
32.00 |
|
100.00 |
27.80 |
24.80 |
|
24.50 |
|
200.00 |
21.80 |
18.80 |
|
10.80 |
|
250.00 |
19.80 |
16.80 |
|
5.50 |
|
Electrical Performance | |
|
Max.Conductor DC Resistance at 20 ℃(Ω/Km) |
<93.8 |
|
Operating Temperature( ℃ ) |
70 |
|
Velocity of propagation |
74% |
|
Impedance(ohm) |
100±15 |