Output
Output Power Capacity: 12 kW / 15 kVA
Max Configurable Power: 12 kW / 15 kVA
Nominal Output Voltage: 230V,400V 3PH
Output Voltage Note
Configurable for 380: 400 or 415 V 3 Phase nominal output voltage
Efficiency at Full Load: 96%
Output Voltage Distortion: Less than 5% at full load
Output Frequency (sync to mains): 47 - 53 Hz for 50 Hz nominal
Crest Factor: Unlimited
Waveform Type: Sine wave
Output Connections
| (1) Hard Wire 4-wire (3PH + G) | |
| (1) Hard Wire 5-wire (3PH + N + G) | |
| (1) Screw Terminals |
Bypass: Built-in Maintenance Bypass,Built-in Static Bypass
Input
Nominal Input Voltage: 400V 3PH
Input Frequency: 40 - 70 Hz (auto sensing)
Input Connections
| Hard Wire 5-wire (3PH + N + G) |
Input voltage range for main operations: 304 - 477V
Other Input Voltages: 380,415
Maximum Input Current: 21A
Input Breaker Capacity: 35A
Input Total Harmonic Distortion: Less than 5% for full load
Batteries & Runtime
Battery Type: Maintenance-free sealed Lead-Acid battery with suspended electrolyte leakproof
Included Battery Modules: 4
Typical recharge time: 5 hour(s)
Replacement Battery: SYBT4
RBC? Quantity: 4
discharge_battery_voltage: +/-154 V
Typical Backup Time At Half Load: 66.4 minutes (6000 Watts)
Typical Backup Time At Full Load: 27.4 minutes (12000 Watts)
Runtime Chart: Smart-UPS VT
Extended Run Options: APC Smart-UPS VT 15KVA 400V w/4 Batt Mod Exp to 4, Int Maint Bypass, Parallel Capable
Communications & Management
Interface Port(s): DB-9 RS-232,Smart-Slot
Pre-Installed SmartSlot? Cards: AP9619
Control panel: Multi-function LCD status and control console
Audible Alarm: Audible and visible alarms prioritized by severity
Emergency Power Off (EPO): Yes
Physical
Maximum Height: 1490.00 mm
Maximum Width: 523.00 mm
Maximum Depth: 838.00 mm
Net Weight: 599.09 KG
Shipping Weight: 630.00 KG
Shipping Height: 1643.00 mm
Shipping Width: 650.00 mm
Shipping Depth: 1062.00 mm
Color: Black
Units per Pallet: 1.00
Environmental
Operating Environment: 0 - 40 °C
Operating Relative Humidity: 0%
Operating Elevation: 0-999,9 meters
Storage Temperature: -15 - 45 °C
Storage Relative Humidity: 0%
Storage Elevation: 0-15000 meters
Audible noise at 1 meter from surface of unit: 54.00 dBA
Online Thermal Dissipation: 2170.00 BTU/hr
Protection Class: IP 20
Conformance
Regulatory Approvals: C-tick,CE,EN 50091-2,EN/IEC 62040-3,IEC 61000-3-2,IEC 61000-3-3,ISO 14001,ISO 9001,VFI-SS-112
Standard Warranty: 1 year on-site repair or replace with factory authorized Start-Up
The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS.