Main technical data | ||
|
rated voltage |
12kV | |
|
rated current |
630A | |
|
rated frequency |
50Hz | |
|
rated short-time power frequency withstand voltage |
42kV | |
|
rated lightring impulse withstand voltage |
75kV | |
|
rated short-circuit breaking current |
12.5/16/20KA | |
|
rated short-circuit making current |
31.5/40/50kA | |
|
rated operations of short-circuit breaking current interruption |
30 times | |
|
rated single capacitor bank breaking current |
400A | |
|
rated short-time withstand current |
12.5/16/20KA | |
|
rated peak withstand current |
31.5/40/50kA | |
|
rated duration of short-circuit |
4s | |
|
mechanical life |
10000times | |
|
contact closing force due to bellows and atmosphere |
70±40N | |
|
counterforce at rated contact stroke |
120±50N | |
|
circuit resistance at rated contact force |
≤20μΩ | |
|
shelf life |
20years | |
|
contact erosion limit |
3mm | |
|
weight of moving parts |
≤0.7kg | |
|
mechanical data required for matched vacuum interrupter | ||
|
rated contact stroke |
9±1mm | |
|
average opening speed |
1.0±0.25m/ | |
|
average closing speed |
0.65±0.15m/s | |
|
added contact force |
900/1300/1600±100N | |
|
contact bouncing duration at closing operation |
≤2ms | |
|
contact bouncing bank amplitude of opening operation |
≤2mm | |
|
three-pole simultaneity |