Main technical data | ||
rated voltage |
12kV | |
rated current |
630A | |
rated frequency |
50Hz | |
rated short-time power frequency withstand voltage |
42kV | |
rated lightring impulse withstand voltage |
75kV | |
Rated short-time withstand current |
16/20 KA | |
Rated withstand current |
40/50KA | |
rated short-circuit making current |
40/50KA | |
rated cloaed-loop breaking current |
630A | |
rated active load breaking current |
630A | |
rated cable charging breaking current |
10A | |
rated single capacitor bank breaking current |
400A | |
rated duration of short-circuit |
4s | |
mechanical life |
10000 times | |
contact closing force due to bellows and atmosphere |
70±40N | |
counterforce at rated contact stroke |
120±50N | |
circuit resistance at rated contact force |
≤45μΩ | |
shelf life |
20years | |
contact erosion limit |
3mm | |
weight of moving parts |
≤0.6kg | |
mechanical data required for matched vacuum interrupter | ||
rated contact stroke |
9±1mm | |
average opening speed |
1.0±0.2m/s | |
average closing speed |
0.65±0.2m/s | |
added contact force |
700/900±50N | |
contact bouncing duration at closing operation |
≤2ms | |
contact bouncing bank amplitude of opening operation |
≤2mm | |
three-pole simultaneity |
≤1ms |