Product Main

Specifications

Main technical data
rated voltage 
12kV   
rated current 
250/400/630A
rated frequency
50Hz
rated short-time power frequency withstand voltage  
42kV
rated lightring impulse withstand voltage 
75kV
rated making  current     
2.5/4.0/6.3KA
rated breaking current ,max             
2.0/3.2/5.0kA
rated breaking current ,min 
50/80/125 kA
rated making current ,limit   
2.5/4.0/6.3 kA
rated short-time withstand current  
2.5/4.0/6.3 kA
rated duration of short-circuit 
4s
mechanical life 
30×10000times
Electricity life AC-3  
25×10000 times
Electricity life AC-4  
10×10000 times
Rated contact stroke  
6±1mm
Contact closing force due to bellows and atmosphere
70±30N
counterforce at rated contact stroke  
110±40N
circuit resistance at rated contact atmosphere force                   
≤150μΩ
shelf life                      
20years
contact erosion limit                                   
3mm
weight of moving parts
≤0.6kg
     mechanical data required for matched vacuum interrupter
added contact stroke  
 110±10N
average opening speed                          
0.6±0.2m/s
average closing speed  
0.3±0.1m/s
contact bouncing  duration at closing operation
≤2ms
contact bouncing bank amplitude of opening operation  
≤2mm
three-pole simultaneity  
≤1ms