Main technical data | ||
rated voltage |
12kV | |
rated current |
250/400/630A | |
rated frequency |
50Hz | |
rated short-time power frequency withstand voltage |
42kV | |
rated lightring impulse withstand voltage |
75kV | |
rated making current |
2.5/4.0/6.3KA | |
rated breaking current ,max |
2.0/3.2/5.0kA | |
rated breaking current ,min |
50/80/125 kA | |
rated making current ,limit |
2.5/4.0/6.3 kA | |
rated short-time withstand current |
2.5/4.0/6.3 kA | |
rated duration of short-circuit |
4s | |
mechanical life |
30×10000times | |
Electricity life AC-3 |
25×10000 times | |
Electricity life AC-4 |
10×10000 times | |
Rated contact stroke |
6±1mm | |
Contact closing force due to bellows and atmosphere |
70±30N | |
counterforce at rated contact stroke |
110±40N | |
circuit resistance at rated contact atmosphere force |
≤150μΩ | |
shelf life |
20years | |
contact erosion limit |
3mm | |
weight of moving parts |
≤0.6kg | |
mechanical data required for matched vacuum interrupter | ||
added contact stroke |
110±10N | |
average opening speed |
0.6±0.2m/s | |
average closing speed |
0.3±0.1m/s | |
contact bouncing duration at closing operation |
≤2ms | |
contact bouncing bank amplitude of opening operation |
≤2mm | |
three-pole simultaneity |
≤1ms |