Main technical data | ||
|
rated voltage |
7.2kV | |
|
rated current |
250/400/630A | |
|
rated frequency |
50Hz | |
|
rated short-time power frequency withstand voltage |
42kV | |
|
rated lightring impulse withstand voltage |
75kV | |
|
rated making current |
2.5/4.0/6.3KA | |
|
rated breaking current ,max |
2.0/3.2/5.0kA | |
|
rated breaking current ,min |
50/80/125 kA | |
|
rated making current ,limit |
2.5/4.0/6.3 kA | |
|
rated short-time withstand current |
2.5/4.0/6.3 kA | |
|
rated duration of short-circuit |
4s | |
|
mechanical life |
30×10000times | |
|
Electricity life AC-3 |
25×10000 times | |
|
Electricity life AC-4 |
10×10000 times | |
|
Rated contact stroke |
6±1mm | |
|
Contact closing force due to bellows and atmosphere |
70±30N | |
|
counterforce at rated contact stroke |
110±40N | |
|
circuit resistance at rated contact atmosphere force |
≤150μΩ | |
|
shelf life |
20years | |
|
contact erosion limit |
3mm | |
|
weight of moving parts |
≤0.6kg | |
|
mechanical data required for matched vacuum interrupter | ||
|
added contact stroke |
110±10N | |
|
average opening speed |
0.6±0.2m/s | |
|
average closing speed |
0.3±0.1m/s | |
|
contact bouncing duration at closing operation |
≤2ms | |
|
contact bouncing bank amplitude of opening operation |
≤2mm | |
|
three-pole simultaneity |