* Power Fuse(Expulsion Type)
<Electricity>
STATION Type Fuse Ratings
JFM-20
(Indoor Type) JFU-20
1K~200K
kV Ampere(rms)
Nom. Max. Des. BIL Max. Interrupting
25.8 27 125 200K Sym. Asym.
12,500 20,000
SM-40
(Indoor Type) SMU-40
300E~400E 25 29 150 400E 20,000 32,000
SMD-40
(Outdoor Type) SMU-40
300E~400E 25 29 150 400E 20,000 32,000
DROP-OUT JFD-20
(Indoor Type) JFU-20
15~200K 25.8 27 150 200K 12,500 20,000
Rated Capacity of Transformer
(kVA) Rated Full-load
Current of Transformer
In[A] Magnetizing and
Inrush Current of Transformer [A]
If=10In r.m.s value of symmetrical
Short-circuit current Is=[A]
100In/% Z Fuse
Rating Selection Range
1? 3? Minimum maximum
- 5 0.13 1.3 2.10 1K 3K
- 7.5 0.19 1.9 3.15 1K 3K
- 10 0.25 2.5 4.2 1K 3K
5 15 0.38 3.8 6.3 1K 3K
6.67 20 0.50 5.0 8.4 1K 3K
10 30 0.76 7.6 12.6 1K 3K
15 45 1.13 11.3 18.9 3K 6K
25 75 1.89 18.9 31.5 3K 6K
33 100 2.52 25.2 42.0 3K 6K
50 150 3.78 37.8 63.0 6K 6K
67 200 5.04 50.4 84.0 8K 10K
75 225 5.67 56.7 94.5 8K 10K
100 300 7.56 75.6 126.1 10K 12K
167 500 12.6 126 210.1 15K 20K
250 750 18.9 189 315.1 25K 30K
333 1,000 25.2 252 420.2 30K 40K
500 1,500 37.8 378 630.3 50K 65K
667 2,000 50.4 504 840.4 65K 80K
1,000 3,000 75.6 756 1,260.6 100K 140K
1,333 4,000 100.8 1,008 1,680.8 140K 200K
1,667 5,000 126.0 1,260 2,101.0 200K 300E
2,000 6,000 151.2 1,512 2,521.2 200K 300E
2,500 7,500 189.0 1,890 3,151.5 300E 400E
3,333 10,000 252.0 2,520 4,202.0 300E 400E