Product Main

Specifications

Item Name: GTM9 series Moulded Case Circuit Breaker

The breaker is mainly used in distribution network of AC 50Hz or 60Hz, rated voltage up to 690V, rated working current up tp 630A to distribute electric power and to protect the line and the equipment from being damage due to overload, Short circuit and under-voltage. It can also be used fro unfrequent motor start and for motor overload, short circuit and under voltage protections.

Standard: IEC 60947-2
Type GTM9-63 (Thermal Magnetic) GTM9-125 (Thermal Magnetic) GTM9-250
(Thermal Magnetic)
GTM9-400
(Thermal Magnetic)
GTM9-630
(Thermal Magnetic)
GTM9-800
(Thermal Magnetic)
Frame
current(A)
63 125 250 400 630 800
Frame
current(A)
10A, 16A,
20A, 25A,
32A, 40A,
50A, 63A
16-25A,
25-40A,
40-63A,
63-100A,
80-125A
(adjustable)
125-160A,
160-250A
(adjustable)
250A, 310A, 350A, 400A 400,
500A,
630A
630A,
700A,
800A
Pole 3 3, 4 3, 4 3, 4 3, 4 3, 4
Rated insulating voltage(V) 690 690 690 690 690 690
Breaking capacity grade S S H S H S H S H S H
Rated breaking capacity Icu (KA) AC
400V
18/0.3 36/0.25 50/0.25 36/0.25 50/0.25 65/0.2 85/0.2 65/0.2 85/0.2 65/0.2 85/0.2
AC
690V
/ 8/0.5 20/0.3 8/0.5 20/0.3 15/0.3 20/0.3 15/0.3 20/0.3 15/0.3 20/0.3
Rated limit short circuit breaking capacity Icu (KA) AC
400V
25/0.25 36/0.25 50/0.25 36/0.25 50/0.25 65/0.2 85/0.2 65/0.2 85/0.2 65/0.2 85/0.2
AC
690V
/ 8/0.5 20/0.3 8/0.5 20/0.3 15/0.3 20/0.3 15/0.3 20/0.3 15/0.3 20/0.3
More Product Features
HS Code: 85362000
Standard: Iec 60947-2
Speed: Normal Type Circuit Breaker
Structure: Moulded Case Circuit Breaker
Operation: Electric Type
Breaking Capacity: Low Voltage Circuit Breakers


We always pursuer the promise of " credit first, service best" facing the market home and abroad, wish to build and strengthen the close cooperation with the customers march with you hand in hand and creating the bright future.