electrical contactor/ac contactor/ contactor

Application

CJX2 series AC Contactor is suitable for using in the circuits up to the rated voltage 660V AC 50Hz or 60Hz, rated current up to 95A, for making, breaking, frequently starting & controlling the AC motor. Combined with the auxiliary contact block, timer delay & machine-interlocking device etc, it becomes the delay contactor, mechanical interlocking contactor, star-delta starter. With the thermal relay, it is combined into the electromagnetic starter. The Contactor is produced according to IEC947-2, VDE0660 & BS5452.

Type

CJX2-D09

CJX2-D12

CJX2-D18

CJX2-D25

CJX2-D32

Rated working
current(A)

AC3

9

12

18

25

32

AC4

3.5

5

7.7

8.5

12

AC3 capacity of phase 3 squirrel-cage motor AC3(KW)

220/230V

2.2

3

4

5.5

7.5

380/400V

4

5.5

7.5

11

15

415V

4

5.5

9

11

15

440V

4

5.5

9

11

15

500V

5.5

7.5

10

15

18.5

660/690V

5.5

7.5

10

15

18.5

Rated heat current(A)

20

20

32

40

50

Electrical life

AC4X104

20

20-15

20-7

15-7

15-7

AC3X106

2

2

2

2

2

Mechanical

20

20

20

20

20

number of the contact

3P+NO

3P+NC

Specifications:

Volts
(VAC)

24

42

48

110

220/230

230

240

380/400

400

415

440

500

660

50Hz

B5

D5

E5

F5

M5

P5

U5

Q5

V5

N5

R5

S5

Y5

60Hz

B6

D6

E6

F6

M6

-

U6

Q6

-

-

R6

-

-

50/60Hz

B7

D7

E7

F7

M6

P7

U7

Q7

V7

N7

R7

-

-

Type

CJX2-D40

CJX2-D50

CJX2-D65

CJX2-D80

CJX2-D95

   

40

50

65

80

95

 

18.5

24

28

37

44

AC3 capacity of phase 3 squirrel-cage motor AC3(KW)

220/230V

11

15

18.5

22

25

380/400V

18.5

22

30

37

45

415V

22

25

37

45

45

440V

22

30

37

45

45

500V

22

30

37

55

55

660/690V

30

33

37

45

45

Rated heat current(A)

60

80

80

125

125

 

AC4X104

10-7

7

7-6

7-5

7-5

AC3X106

2

2

1.6

1.6

1.6

Mechanical

20

20

20

10

10

number of the contact

3P+NC+NO