Item Name: Indoor AC HV Vacuum Circuit Breaker (VS1)
ZN63-12(VS1) Indoor AC high voltage vacuum circuit-breaker series in the power system of three-phase AC, 50Hz and 10 kV to function as switching different kinds of leads or the loads needing frequent operation, and can protect and control electric equipment in the industrial & mineral enterprise, power plant and substation as well. It can coordinate with the KYN28A-12(GZS1) middle-arranged manual-driven switchgear or XGN-fixed switchgear as well.
Conform the standard: IEC 60056, GB198489, JB3855, DL/T403.
ZN63-12(VS1) Indoor AC high voltage vacuum circuit-breaker series in the power system of three-phase AC, 50Hz and 10 kV to function as switching different kinds of leads or the loads needing frequent operation, and can protect and control electric equipment in the industrial & mineral enterprise, power plant and substation as well. It can coordinate with the KYN28A-12(GZS1) middle-arranged manual-driven switchgear or XGN-fixed switchgear as well.
Conform the standard: IEC 60056, GB198489, JB3855, DL/T403.
No. | Item | Unit | Data | |||
1 | Rated voltage | KV | 12 | |||
2 | Rated frequency | Hz | 50 | |||
3 | Rated lighting impulse withstand voltage (peak) | KV | 75 | |||
4 | Rated short time withstand voltage (1 min) | KV | 42 | |||
5 | Rated short time breaking current | KA | 20 | 25 | 31.5 | 40 |
6 | Rated current | A |
630 1250 |
630 1250 |
630, 1250 1600, 2000 2500, 3150 |
1600, 2000 2500, 3150 |
7 | Rated short time withstand current (virtual value) | KA | 20 | 25 | 31.5 | 40 |
8 | Rated peak withstand current (peak) | KA | 50 | 63 | 80 | 100 |
9 | Rated short-circuit closing current (peak) | KA | 50 | 63 | 80 | 100 |
10 | Rated short-circuit current duration | s | 4 | |||
11 | Rated short-circuit current breaking time | times | 50 (for 40KA is 30) | |||
12 | Mechanism life | Times | 2000 | |||
13 | Secondary circuit power frequency withstand voltage (1 min) | V | 2000 | |||
14 | Rated operation order | O-0.3S-CO-180S-CO | O-180S-CO-180S-CO | |||
15 | Rated unit/ back-to-back capacitor bank breaking current | A | 630/400 (for 40Ka is 800/4000 | |||
16 | Rated capacitor bank closing inrush current | KA | 12.5(frequency is not higher than 1000HZ) | |||
17 | Contact opening distance | mm | 11± 0.1 | |||
18 | Contact supper travel | mm | 3.5± 0.5 | |||
19 | Contact closing tripping time | ms | ≤ 2 | |||
20 | Three-phase breaking /closing non-synchronism | ms | ≤ 2 | |||
21 | Average switch-off speed | m/s | 1± 0.2 | |||
22 | Average switch-on speed | m/s | ||||
23 | Switch-off (rated voltage) | ms | 20~60 | |||
24 | Switch-on (rated voltage0 | ms | 30~70 | |||
25 | Rated switch-on/off operating voltage | V | AC110/220, DC110/220 | |||
26 | Energy storage motor rated voltage | V | AC110/220, DC110/220 | |||
27 | Motor rated rate of work | W | 70(40KA 100W) | |||
28 | Energy storing time | s | ≤ 15 | |||
29 | Contact erosion limit | mm | 3 | |||
30 | Break-brake rebound amplitude | mm | ≤ 3 | |||
31 | Main conducting loop resistance |
630A 1250A 1600-2000A 2500 and above |
≤ 65μ Ω ≤ 55μ Ω ≤ 45μ Ω ≤ 35μ Ω |
|||
32 | Contact switch-on pressure |
20KA 25KA 31.5KA 40KA |
(2000± 200)N (2400± 200)N (3100± 200)N (5000± 300)N |
More Product Features
HS Code: | 85362000 |
---|---|
Trademark: | JUBANG |
Model NO.: | VS1 |
Standard: | IEC60056 |
Shipment Terms: | FOB |
Payment Terms: | T/T |
Minimum Order: | 2 Pieces |
Origin: | China |
Packing: | Wooden Case |
Type: | Circuit Breaker |
Function: | Circuit-Breaker Failure Protection |
Certification: | CE |
Installation: | Fixed |
Speed: | Normal Type Circuit Breaker |
Arc-extinguishing Medium: | Vacuum |
Structure: | Vacuum Circuit Breaker |
Operation: | Electric Type |
Breaking Capacity: | High Voltage Circuit Breakers |
Export Markets: | South America, Eastern Europe, Southeast Asia, Africa, Mid East, Eastern Asia, Western Europe |
Company: | Jubang Electric Co., Ltd. |