Product Main

Specifications

AAAC-6201
Code Word Size            (kcmil) Strand-ing Diameter              (ins.) Cross-   Sectional       Area              (Sq.ins.)          Weight        Per               1000 ft.            (lbs.) Rated          Strength      (lbs.) Resistance                  OHMS/1000 ft. Allowable Ampacity+          (Amps) ACSR With          Equiv.Diam. Approx.            EC Cond.       With              equivalent            Resistance
Individual      Wire Complete     Cables DC @            20℃ AC @            75℃ Size Stranding            (AL/STL)
Akron 30.58 7 0.0661 0.198 0.0240 28.5 1110 0.659 0.785 107 6 6/1 6
Alton 48.69 7 0.0834 0.25 0.0382 45.4 1760 0.414 0.493 143 4 6/1 4
Ames 77.47 7 0.1052 0.316 0.0608 72.2 2800 0.26 0.310 191 2 6/1 2
Ames 77.47 7 0.1052 0.316 0.0608 72.2 2800 0.26 0.310 191 2 6/1 2
Azusa 123.3 7 0.1327 0.398 0.0968 115 4460 0.163 0.195 256 1/0 6/1 1/0
Azusa 123.3 7 0.1327 0.398 0.0968 115 4460 0.163 0.195 256 1/0 6/1 1/0
Anaheim 155.4 7 0.149 0.447 0.1221 144.9 5390 0.13 0.154 296 2/0 6/1 2/0
Amherst 195.7 7 0.1672 0.502 0.1537 182.5 6790 0.103 0.123 342 3/0 6/1 3/0
Alliance 246.9 7 0.1878 0.563 0.1939 230.2 8560 0.0816 0.0973 395 4/0 6/1 4/0
Alliance 246.9 7 0.1878 0.563 0.1939 230.2 8560 0.0816 0.0973 395 4/0 6/1 4/0
Butte 312.8 19 0.1283 0.642 0.2456 291.7 11000 0.0644 0.0769 460 266.8 26/7 266.8
Canton 394.5 19 0.1441 0.72 0.3099 367.9 13300 0.0511 0.061 532 336.4 26/7 336.4
Cairo 465.4 19 0.1565 0.783 0.3655 434 15600 0.0433 0.0518 590 397.5 26/7 397.5
Darien 559.5 19 0.1716 0.858 0.4394 521.7 18800 0.036 0.0431 663 477 26/7 477.0
Elgin 652.4 19 0.1853 0.927 0.5124 608.4 21900 0.0309 0.0371 729 556.5 26/7 556.5
Flint 740.8 37 0.1415 0.99 0.5818 690.8 24400 0.0272 0.0327 790 636 26/7 636.0
Greeley 927.2 37 0.1583 1.108 0.7282 864.6 30500 0.0217 0.0263 908 795 26/7 795.0
           
+Ampacity based on 75℃ conductor temperature,25℃ ambient temperature,2 ft/sec.wind in sun,emissivity 0.5,52.5% conductivity.