Product Main

Specifications

the main parameters of 220KV current transformer:

Digital photoelectrical current transformer 220KV

Rating current:  1003150A

Rated frequency: 50Hz

Highest voltage for equipment:  252kV

Accuracy classto reach: 0.2S/5TPE pairs of sets

Rated short-term frequency voltage tolerance: 460 kV

Rated lightning impulse withstand voltage: 1050  kV

Rated short time thermal current: 31.5,50 kA

Rated dynamic stability current: 80,125  kA

According to: IEC600448

Equipment type: outdoor

Weight: 220Kg

Climb away from the external insulation ≥6700mm

                                 the main parameters of 110KVcurrent transformer:

Digital photoelectrical current transformer 110KV

Rating current:  1003150A

Rated frequency: 50Hz

Highest voltage for equipment:  126kV

Accuracy classto reach: 0.2S/5TPE pairs of sets

Rated short-term frequency voltage tolerance: 230 kV

Rated lightning impulse withstand voltage: 550  kV

Rated short time thermal current: 31.5,50 kA

Rated dynamic stability current: 80,125  kA

According to: IEC600448

Equipment type: outdoor

Weight: 200Kg

Climb away from the external insulation ≥3800mm