Supension Composite insulator end fittings | |||||
All the end fittings listed in the table below refer to what is stated in IEC 61466(02-1997)standard. | |||||
TYPE
|
Code
|
70KN
|
120KN
|
160KN
|
210KN
|
Size 17
|
Size 24
|
Size 24
|
Size 25
|
||
A=44 | A=62 | A=62 | A=70 | ||
EYE
|
B=20 | B=26 | B=26 | B=26 | |
E
|
C=31 | C=52 | C=52 | C=52 | |
D=45 | D=70 | D=70 | D=74 | ||
E=12 | E=18 | E=18 | E=22 | ||
Y-CLEVIS
|
Size 199 | Size 19 | Size 19 | Size 22 | |
Y
|
H=40 | H=40 | H=40 | H=40 | |
|
|||||
Rod suspension composite insulators Technical Particualars
|
Code No
|
Rated Voltage
(KV) |
Specified Mechanical
Load |
Section
Length |
Min Arc
Distance (mm) |
Leakage Distance (mm) |
Lightning Impulse
Withstand BIL(KV) |
Power
Frequence Withstand (wet) (KV) |
FXYW4-10/70
|
10
|
70
|
350
|
180
|
400
|
95
|
45
|
FXYW4-12/70
|
12
|
70
|
350
|
180
|
400
|
95
|
45
|
FXYW4-24/70
|
24
|
70
|
550
|
370
|
850
|
185
|
95
|
FXYW4-24/100
|
24
|
100
|
570
|
370
|
850
|
185
|
95
|
FXYW4-35/70
|
35
|
70
|
650
|
450
|
1000
|
230
|
105
|
FXYW4-35/100
|
35
|
100
|
670
|
450
|
1000
|
230
|
105
|