KJX1-N series magnetic contactors is suitable for using the circuit up to the rated voltage 660V AC 50HZ or 60HZ,rated current up to 95A, for making, breaking, frequently starting and controlling the AC motor. Combined with the auxiliary contact block,timer delay and machine interlocking device etc., it becomes the delay contactor, mechanical interlocking contactor, star-delta starter. With the thermal relay. It is combined into the electromagnetic starter. The contactor is produced according to IEC60947-4-1
TYPE |
KJX1-N09 |
KJX1-N12 |
KJX1-N18 |
KJX1-N25 |
KJX1-N32 | |
RATED WORKING CURRENTA |
AC3 |
9 |
12 |
18 |
25 |
32 |
AC4 |
3.5 |
5 |
7.7 |
8.5 |
12 | |
AC3 CAPACITY OF PHASE 3 SQUIRRELCAGEMOTER AC3KW |
200/230V |
2.2 |
3 |
4 |
5.5 |
7.5 |
380/440V |
4 |
5.5 |
7.5 |
11 |
15 | |
415V |
4 |
5.5 |
9 |
11 |
15 | |
440V |
4 |
5.5 |
9 |
11 |
15 | |
500V |
5.5 |
7.5 |
10 |
15 |
18.5 | |
660/690V |
5.5 |
7.5 |
10 |
15 |
18.5 | |
RATED HEAT CURRENTA |
20 |
20 |
32 |
40 |
50 | |
ELECTRICAL LIFE |
AC4*10000 |
20 |
20-15 |
20-7 |
15-7 |
15-7 |
AC3*1000000 |
2 |
2 |
2 |
2 |
2 | |
MECHANUCAL LIFE*1000000 |
20 |
20 |
20 |
20 |
20 |
20 |
NUMBER OF THE CONTACTS |
3P+NO | |||||
3P+NC |