Ⅰ.Brief Introduction
 ETCR4100 Double Clamp Digital Phase Meter is a well-developed meter specifically designed for field testing, featuring high accuracy, high stability, low power consumption, easiness to use and so on. It can directly measure phases between two voltages, two currents and phase between the voltage and current; in addition, it can also be used to distinguish three-phase sequence, transformer wiring group, inductive and capacitive circuits, test second circuit and bus differential protection systems, read the phase  relationship between CTs of the differential protection, etc.
ETCR4100 Double Clamp Digital Phase Meter has a large LCD screen displaying words as high as 40mm against a blue backlight, and looks exquisite and comfortable.
ETCR4100 Double Clamp Digital Phase Meter applies to electric power, petroleum chemical industry, metallurgy, railway, and meteorology, industrial and mining enterprises, scientific research institutions, measurement sector and so on.
2.  Technical Specification
1). Base Conditions and Working Conditions

Influence Quantity
Base Condition
Working Conditions
Remark
Ambient Temp
23℃±1℃
-10℃~40℃
 
Ambient Humidity
40%~60%
<80%
 
Signal Waveform
sine wave
sine wave
β=0.05
Signal Frequency
50HZ±1HZ
45HZ~65HZ
 
Meter Working Volt
9V±0.1V
9V±1V
 
External Electric,
Magnetic Field
To be avoided
Measured Wire
Position
Measured wire at approximately the geometric center of the clamp

 
2). General Specification

Function
Phase, direct test of phase sequence; transformer
groups, inductive, capacitive circuit discrimination
Power
DC9V alkaline batteries(1.5V AA×6)
Consumption
About 35mA at most with enabled backlight, battery working continuously Consumption for about 40 hours
About 5mA with disabled backlight, battery working continuously for about 300 hours
Display Mode
LCD display, blue backlight, suitable for dark
places
LCD Size
70mm×62mm
LCD Display Field
64mm×54mm
Meter Size
Length, Width, Height:196*92*54(mm)
Clamp Size
φ7.5mm*13mm
Sampling Rate
About 3 times/second
Measurement  Range
0~360°
Intrinsic Error
±3°
Resolution
±1°
Measured Signal Amplitude in Phase Test
U1-U2 phase test:30V~500V
I1-I2 phase test:10mA~10.00A
U1-I2 or I1-U2 phase test:10V~500V,10mA~10.00A
Data Hold
Press HOLD key to keep data, "DH" symbol appears
Automatic Shutdown
Automatic shutdown about 15 minutes later after  launching to reduce battery consumption
Voltage Detection
Low battery symbol " " appears to remind  the replacement of battery when the battery voltage drops below 7.8V~8V.
Weight
Main Unit about 550g(with battery),clamp about 170g×2,test line about 250g
Test Line Length
1.5m
Current Clamp Length
2m
Working  Temperature and Humidity
-10℃~40℃; below 80%Rh
Input Impedance
Input impedance for voltage range:2MΩ
Input impedance when testing U1U2 phase:40KΩ
Withstand Voltage
Withstand 1000V/50Hz sine wave AC voltage for 1 minute between the meter lines and shell;
Withstand 500V/50Hz AC voltage sine wave for 1 minute between the two voltage inputs
Insulation
≥10MΩ between meter lines and shell or between
the two voltage inputs
Structure
Double insulation
Packing
Host: 1pcs; Meter Box: 1pcs; Current Clamp: 2pcs; Test Line: 4pcs(2 Red and 2 Black);