Product Main

Specifications

Application:
    CJX2 series AC Contactor is applicable in the circuit rated voltage up to 1000V AC. 50/60HZ, rated current up to 780A, for long distance breaking circuit and frequently starting or controlling the motor. It also can be used for the control of distributing circuits of rated current from 200A to 1600A (AC-1)/115A to 780A (AC-3).

 

Specification:
Type Rated operation current(A) Standard power ratings of 3-phase motors AC-3(KW)
AC-3 AC-1 220/230V 380/400V 415V 440V 500V 660/690V 1000V
LC1-F115   (CJX2-F115) 115 200 30 55 59 59 75 80 65
LC1-F150   (CJX2-F150) 150 280 40 75 80 80 90 100 65
LC1-F185   (CJX2-F185) 185 275 55 90 100 100 110 110 100
LC1-F225   (CJX2-F225) 225 315 63 110 110 110 129 129 100
LC1-F265   (CJX2-F265) 265 350 75 132 140 140 160 160 147
LC1-F330   (CJX2-F330) 330 400 100 160 180 200 200 200 160
LC1-F400   (CJX2-F400) 400 500 110 200 200 250 257 280 185
LC1-F500   (CJX2-F500) 500 700 147 250 280 295 355 335 335
LC1-F630   (CJX2-F630) 630 1000 200 335 375 400 400 450 450
LC1-F780   (CJX2-F780) 780 1600 220 400 425 425 450 475 450