Product Main

Specifications

Application
 
CJX2-D series AC Contactor is suitable for using in the circuits up to the rated voltage 660V AC 50Hz or 60Hz, rated current up to 620A, for making, breaking, frequently starting & controlling the AC motor. Combined with the auxiliary contact block, timer delay & machine-interlocking device etc, it becomes the delay contactor, mechanical interlocking contactor, star-delta starter. With the thermal relay, it is combined into the electromagnetic starter. The products comply with IEC60947-4.
 
Specifications:
 
Model)
D09
D12
D18
D25
D32
D40
D50
D65
Rated working
current (A)
AC3
9
12
18
25
32
40
50
65
AC4
3.5
5
7.7
8.5
12
18.5
24
28
AC3 capacity of phase 3 squirrel-cage motor AC3(KW)
220/230V
2.2
3
4
5.5
7.5
11
15
18.5
380/400V
4KW
5.5
7.5
11
15
18.5
22
30
415V
4KW
5.5
9
11
15
22
25
37
500V
5.5KW
7.5
10
15
18.5
22
30
37
660/690V
5.5KW
7.5
10
15
18.5
30
33
37
Rated heat current (A)
20
20
32
40
50
60
80
80
Compatible manual or auto thermal overload relays
AC3 x 104
100
100
100
100
80
80
60
60
AC4 x 104
20
20
20
20
20
15
15
15
Mechanical life x 104
1000
1000
1000
1000
800
800
800
800
Number of the contacts
3P+NO
3P+NC+NO
3P+NC
 
 
Dimension & Mounting Size
 
For CJX2-D09~95 contactors:
 
 
Type
A
B
C
D
E
a
b
CJX2-D09~12
47
76
82
113
133
34/35
50/60
4.5
CJX2-D18
47
76
87
118
138
34/35
50/60
4.5
CJX2-D25
57
86
95
126
146
40
48
4.5
CJX2-D32
57
86
100
131
151
40
48
4.5
CJX2-D40~65
77
129
116
145
165
40
100/110
6.5
CJX2-D80~95
87
129
127
175
195
40
100/110
6.5
 
Standard Control Circuit Voltages
 
Volts
24
42
48
110
220
230
240
380
400
415
440
500
660
50Hz
B5
D5
E5
F5
M5
P5
U5
Q5
V5
N5
R5
S5
Y5
60Hz
B6
D6
E6
F6
M6
-
U6
Q6
-
-
R6
-
-
50/60Hz
B7
D7
E7
F7
M7
P7
U7
Q7
V7
N7
R7
-
-
 
D80
D95
D115
D150
D170
D205
D245
D300
D410
D475
D620
80
95
115
150
170
205
245
300
410
475
620
37
44
52
60
75
85
105
117
138
147
180
22
25
30
40
55
63
75
100
110
147
200
37
45
55
75
90
110
132
160
220
265
335
45
45
59
80
100
110
132
180
220
280
375
55
55
75
90
110
129
160
200
250
355
400
45
55
80
100
110
129
160
220
280
355
450
125
125
200
250
250
275
315
400
500
700
1000
60
60
200
60
60
50
50
50
30
30
20
10
10
15
15
15
15
15
15
8
8
5
600
600
300
300
300
300
300
300
100
100
100
3P+NC+NO
-
-
 
For TSC1-D115~620 contactors:
 
 
Type
A
B
C
b1
P
Q
S
Q1
M
N
L
Ga
Ha
CJX2-D115
158
120
132
158
35
60
17
25
134
96.2
75
M6
-
-
CJX2-D150
158
120
132
158
35
60
17
25
134
96.2
75
M6
-
-
CJX2-D170
158
120
132
158
35
60
17
25
134
96.2
75
M6
-
-
CJX2-D205
168.5
174
181
137
40
69
20
59.4
154
127
113.5
M8
80
120-106
CJX2-D245
168.5
197
181
137
48
69
25
51.5
172
127
113.5
M10
80
120-106
CJX2-D300
213
206
219
145
48
91
25
74
181
158
145
M10
80
120-106
CJX2-D410
213
206
219
209
48
91
25
74
181
158
145
M10
80
120-106
CJX2-D475
233
238
232
209
55
108
30
77
208
172
146
M10
80
180
CJX2-D620
309
309
255
280
80
140
4
89
264
202
155
M12
80