Product Main

Specifications

Arrester type(10KA) Rated voltage MCOV(KV) Steep current impulse 1/10ms lighting impulse 8/20ms Switching current impulse 30/60ms 2000ms rectangular current withstand(A) 4/10ms high current impulse Dimesion(Total length)mm Dimension(insulator part)mm No. of sheds Creepage distance(mm)
HDA1-10/6 6 4.8 20.7 18 15.3 250 100 250 125 3 210
HDA1-10/9 9 7.2 31.0 27 23.0 250 100 280 155 4 280
HDA1-10/11 11 8.8 37.9 33 28.1 250 100 310 185 5 350
HDA1-10/12 12 9.6 41.5 36 30.6 250 100 310 185 5 351
HDA1-10/15 15 12.0 52.0 45 38.3 250 100 340 215 6 419
HDA1-10/18 18 14.4

62.0

54 46.0 250 100 370 245 7 487
HDA1-10/21 21 16.8 72.5 63 53.5 250 100 400 275 8 555
HDA1-10/24 24 19.2 82.5 72 61.2 250 100 430 305 9 622
HDA1-10/27 27 21.6 93.2 81 69.0 250 100 460 335 10 690
HDA1-10/30 30 24.0 103.5 90 76.5 250 100 520 395 12 760
HDA1-10/33 33 26.4 113.8 99 84.2 250 100 550 425 13 894
HDA1-10/36 36 28.8 124.2 108 91.8 250 100 550 425 13 894

 

Polymer Housed Metal-Oxide Surge Arrester
the best advantage protection against over-voltage
1.Series 1-Polymer housed metal-oxide surge arrester
2.Series 2-Polymer housed metal-oxide surge arrester
3.Series 3-Porcelain Housed metal-oxide surge arrester
4.Series 3-station class surge arresters

Operating principle
1.Metal-oxide surge arrester provides the most advanced protection against over-voltage in the world,since MOA' resistors are made up of zinc oxide films.
2.MOA has a good voltage-ampere characteristics as compared with silicone carbide arrester,its volt/ampere characteristic is much superior and results in much better performance.
3.A micro ampere level current flows while MOA is operating under normal voltage,but the amount of the current will be thousands amperes when MOA is subjected to over-voltage,because of MOA has a good non-linear characteristics,Hence MOA provide excellent protection for the HV equipment,especially the transformer,cables and switchgear.

Application
Metal-oxide surge arrester which applies to protect the power equipment link transformers against system overvoltage and lighting surges.

Service conditions
1.Ambient temperature:-40degrees to +40degrees
2.Height about sea level:<=1000m
3.Power supply frequency:48-62HZ
4.Earthquake intensity:Not exceed richter 7.0 grade
5.Maximum wind veiocity:<=35m/s
6.The long-term power running voltage should not over the continus operating voltage
7.The altiplano or contaminated area should be indicated