Product Main

Specifications

Earth Resistance Tester
Model: ET-2000
CE

ET-2000 of Clamp Earth Tester, in the measurement of a grounding system with loop current, does not require breaking down the grounding wire, and need no auxiliary electrode. It is safe, fast and simple in use.
In According with GB/T 1.1-2000
Safe, Fast response and Simple in use
1 Liquid Crystal Display (LCD)
2 Trigger: to control opening and closing of jaw :
3 Pincer Jaw : 65 x 32mm
4 POWER Key: Boot Up / Shutdown / * Quit
5 HOLD Key: lock / Release display
 
 
Technical Specifications
Power Source
6VDC (4 ×5# alkaline battery)
Working Temperature
-10 ° -55 ° C
Relative Humidity
10%-90%
LCD
4-digital LCD, 47 × 28.5mm in length
Span of Jaw
28mm
Net weight
1160g
Dimension(mm)
285* 85 * 56
Protection Level
Double insulation
Structural Feature
In the jaw way
Shift
Automatic
External Magnetic Field
< 40A/m
External Electric Field
< 1V/m
Measuring Time
1 second
Resistance Measurement Frequency
> 1KHz
Maximum Resistance Measurement resolution
0.001 Ω
Range of Resistance Measurement
0.01-1000 Ω
Accessories
Carry Case(1),Strap(1), 5# Alkaline Battery
Survey pattern
Survey scope
Resolution
Accuracy
Resistance
0.010~0.099(Ω)
0.001(Ω)
±(1%+0.01Ω)
0.10~0.99(Ω)
0.01(Ω)
±(1%+0.01Ω)
1.0~49.9(Ω)
0.1(Ω)
±(1.5%+0.1Ω)
50.0~99.5(Ω)
0.5(Ω)
±(3%+0.5Ω)
100~199(Ω)
1(Ω)
±(3%+1Ω)
200~395(Ω)
5(Ω)
±(6%+5Ω)
400~590(Ω)
10(Ω)
±(10%+10Ω)
600~1000(Ω)
20(Ω)
±(20%+20Ω)