Grand Resistance Tester
Model: ET-2000C
ET-2000C of Pincer Earth Tester, in the measurement of a grounding system with loop current, does not require breaking down the grounding wire, and need no auxiliary electrode. It ia also able to measure the leakage current and the neutral current in the grounding system. It is safe, fast and simple in use.
|
In According with GB/T 1.1-2000 Safe, Fast response and Simple in use 1. Liquid Crystal Display (LCD) 2. Trigger: to control opening and closing of jaw 3 .Pincer Jaw : 65 x 32mm 4 .POWER Key: Boot Up / Shutdown/ * Quit 5 .MODE Key : switch key of function mode (resistance measurement / current measurement /data access) 6. SET Key : function key combinations (Combination with MODE key to achieve: Lock / Release / Storage / Set / Check / Browse / Delete Data) |
|
Technical Specifications |
|
Power Source |
6VDC (4 ×5# alkaline battery) |
|
Working Temperature |
-10 ° -55 ° C |
|
Relative Humidity |
10%-90% |
|
LCD |
4-digital LCD, 47 × 28.5mm in length |
|
Span of Jaw |
28mm |
|
Net weight |
1160g |
|
Dimension(mm) |
285* 85 * 56 |
|
Protection Level |
Double insulation |
|
Structural Feature |
In the jaw way |
|
Shift |
Automatic |
|
External Magnetic Field |
< 40A/m |
|
External Electric Field |
< 1V/m |
|
Measuring Time |
1 second |
|
Resistance Measurement Frequency |
> 1KHz |
|
Maximum Resistance Measurement resolution |
0.001 Ω |
|
Range of Resistance Measurement |
0.01-1000 Ω |
|
Current Measurement Range |
0.00 -20.0A |
|
Current Measurement Frequency |
45-65Hz |
|
Storable Measurement Data |
50 Units |
|
Setting Range of Resistance Alarm Critical Value |
1-199 Ω |
|
Setting Range of Current Alarm Critical Value |
1-499mA |
|
Accessories |
Carry Case(1),Strap(1), 5# Alkaline Battery |
|
Survey pattern |
survey scope |
resolution
|
accuracy |
|
Resistance |
0.010~0.099(Ω) |
0.001(Ω) |
±(1%+0.01Ω) |
|
0.10~0.99(Ω) |
0.01(Ω) |
±(1%+0.01Ω) |
|
1.0~49.9(Ω) |
0.1(Ω) |
±(1.5%+0.1Ω) |
|
50.0~99.5(Ω) |
0.5(Ω) |
±(2%+0.5Ω) |
|
100~199(Ω) |
1(Ω) |
±(3%+1Ω) |
|
200~395(Ω) |
5(Ω) |
±(6%+5Ω) |
|
400~590(Ω) |
10(Ω) |
±(10%+10Ω) |
|
600~1000(Ω) |
20(Ω) |
±(20%+20Ω) |
|
Electric current |
0.00~299 mA |
1 mA |
±(5%+2 mA) |
|
100~299 mA |
1 mA |
±(5%+5 mA) |
|
0.30~2.99 A |
10 mA |
±(5%+0.03 mA) |
|
3.00~9.99 A |
10 mA |
±(5%+0.4 mA) |
|
10.00~20.00 A |
10 mA |
±(5%+0.5 mA) |
|