Grand Resistance Tester
Model: ET-2000C
ET-2000C of Pincer Earth Tester, in the measurement of a grounding system with loop current, does not require breaking down the grounding wire, and need no auxiliary electrode. It ia also able to measure the leakage current and the neutral current in the grounding system. It is safe, fast and simple in use.
 
In According with GB/T 1.1-2000
Safe, Fast response and Simple in use
1. Liquid Crystal Display (LCD)
2. Trigger: to control opening and closing of jaw 3 .Pincer Jaw : 65 x 32mm
4 .POWER Key: Boot Up / Shutdown/ * Quit
5 .MODE Key : switch key of function mode (resistance measurement / current measurement /data access)
6. SET Key : function key combinations (Combination with MODE key to achieve: Lock / Release / Storage / Set / Check / Browse / Delete Data)
Technical Specifications
Power Source
6VDC (4 ×5# alkaline battery)
Working Temperature
-10 ° -55 ° C
Relative Humidity
10%-90%
LCD
4-digital LCD, 47 × 28.5mm in length
Span of Jaw
28mm
Net weight
1160g
Dimension(mm)
285* 85 * 56
Protection Level
Double insulation
Structural Feature
In the jaw way
Shift
Automatic
External Magnetic Field
< 40A/m
External Electric Field
< 1V/m
Measuring Time
1 second
Resistance Measurement Frequency
> 1KHz
Maximum Resistance Measurement resolution
0.001 Ω
Range of Resistance Measurement
0.01-1000 Ω
Current Measurement Range
0.00 -20.0A
Current Measurement Frequency
45-65Hz
Storable Measurement Data
50 Units
Setting Range of Resistance Alarm Critical Value
1-199 Ω
Setting Range of Current Alarm Critical Value
1-499mA
Accessories
Carry Case(1),Strap(1), 5# Alkaline Battery
 
Survey pattern
survey scope
resolution
 
accuracy
Resistance
0.010~0.099(Ω)
0.001(Ω)
±(1%+0.01Ω)
0.10~0.99(Ω)
0.01(Ω)
±(1%+0.01Ω)
1.0~49.9(Ω)
0.1(Ω)
±(1.5%+0.1Ω)
50.0~99.5(Ω)
0.5(Ω)
±(2%+0.5Ω)
100~199(Ω)
1(Ω)
±(3%+1Ω)
200~395(Ω)
5(Ω)
±(6%+5Ω)
400~590(Ω)
10(Ω)
±(10%+10Ω)
600~1000(Ω)
20(Ω)
±(20%+20Ω)
Electric current
0.00~299 mA
1 mA
±(5%+2 mA)
100~299 mA
1 mA
±(5%+5 mA)
0.30~2.99 A
10 mA
±(5%+0.03 mA)
3.00~9.99 A
10 mA
±(5%+0.4 mA)
10.00~20.00 A
10 mA
±(5%+0.5 mA)