UPS:
Output Power Capacity 700 Watts / 1000 VA
Max Configurable Power 700 Watts / 1000 VA
Nominal Output Voltage 230V
Output Voltage Note
Configurable for 220 : 230 or 240 nominal output voltage
Output Voltage Distortion
Less than 5% at full load
Output Frequency (sync to mains) 47 - 53 Hz for 50 Hz nominal,57 - 63 Hz for 60 Hz nominal
Crest Factor up to 5 : 1
Waveform Type Sine wave
Output Connections
(6) IEC 320 C13 |
|
(2) IEC Jumpers |
|
Input
Nominal Input Voltage 230V
Input Frequency 50/60 Hz +/- 3 Hz (auto sensing)
Input Connections
IEC-320-C14 inlet |
|
Input voltage range for main operations 160 - 285V
Input voltage adjustable range for mains operation 151 - 302V
Batteries & Runtime
Battery Type Maintenance-free sealed Lead-Acid battery with suspended Electrolyte : leakproof
Typical recharge time 3 hour(s)
RBC Quantity 1
Typical Backup Time
At Half Load 16.4 minutes (250 Watts)
At Half Load 16.4 minutes (250 Watts)
Typical Backup Time
At Full Load 4.8 minutes (500 Watts)
At Full Load 4.8 minutes (500 Watts)
Communications & Management
Interface Port(s) DB-9 RS-232,USB,SmartSlot
Available SmartSlot Interface Quantity 1
Control panel LED status display with load and battery bar-graphs and On Line : On Battery : Replace Battery : and Overload Indicators Audible Alarm
Alarm when on battery : distinctive low battery alarm : configurable delays
Emergency Power Off (EPO) Optional
Surge Protection and Filtering
Surge energy rating 340 Joules
Filtering Full time multi-pole noise filtering : 0.3% IEEE surge let-through : Zero clamping response time : meets UL 1449