Type:AWR-P1 1.Main power supply: AC 220V (+10%~-15%) .50HZ
2.Back-up power supply: DC 24V.4AH(built-in)
3.Work consumption: Supervising status:≤3W;alarm status:≤10W(all 25 units fire detectors are in fire alarm status)
4.Basic supervise capacity: 2 loops.128 addressable points per loop;
5.External control unit: 5 pieces
6.External control unit contact capacity: DC 30V.1A.
7.Polling cycle: ≤10 seconds(single point continuous searching in abnormal situation)
8.Signal transmission distance: ≤1000 m(RVS-2×1.0mm2);≤1500 m(RVS-2×1.5mm2);
9.Alarm line wiring method : 2-wire bus
10.Voltage in alarm bus : 24V (18V~26V)
11.Operation temperature: 0℃~55℃
12.Relative humidity: ≤95%
13.Black box record number: Be able to keep latest 999 pieces records, including opening machine, close machine, reset, fire alarm, supervising, associated operation and fault alarm).
14.Associated operation programmable number: 100 pieces, including OR1, OR2 & AND logic.
15.Location conversion capacity: 2×250 pieces. Each can have 10 Chinese Words or 20 English characters.
16.Fire alarm output relay :1 set(KA1,KA2), voltage free contact, close when there is fire alarm Fault output relay: 1 set(YA1,YA2).Voltage free contact, close when there is fault