Nominal frequency: 50, 69Hz
For indoor electric divices with rated voltage:> 1 kV
Signal situations:
Threshold voltage: 4-5 V
Uo<10% Un, no voltage signalling (alternative)
Uo>15% Un, voltage signalling
Uo>45% Un, normal voltage signalling
Connecting lead: 1—12 m
Ambient temperature range: -25--+55°C
Safe voltage for interface:< 30 V
Protective system: IP42 (IP54)
Dimensions (WxHxD):96 x 48 x 110 mm, cut dimensions on panel: 91 x 44 mm
Adapted sensors:
Capacitive insulators with 10pF (40.5kV), 15pF (24kV), 20pF (12kV), 40pF(7.2kV), etc.
Caoacitive insulators or bushings with capacitive tap with equivalent coupling capacity and voltage level as mentioned above,Customized for individual solutions.