Product Main

Specifications

FOXB Series Temperature Controller is a universal model controller. Different sensor inputs such as RTD and TC are free to change with the controller, which brings much convenience to users. The well designed software, high quality components and elegant workmanship also provide customers perfect using experience. It is widely used in plastic, biology engineering, metallurgy, packing, chemical and boiler products and industry.

General Electrical Data

Rated voltage

180V AC~240V AC

Power consumption

< =5VA

Insulation Strength

Power supply- input1500V AC  1min

Input-relay output1500V AC  1min

Power supply-relay output1500V AC  1min

Insulation Resistance

Input-relay output> 20MW

Input-power supply> 20MW

Power supply-relay output> 20MW

Working Environment

Ambient temperature0°C ~50°C

Relative humidity35%~85%no condensation

Measuring Data

Input sensor

TC < =100 ohm; RTD< =5 ohm per each conductor

Measuring range

K: (-100 ~1200)        E: (-50 ~600)        J: (-100~800)

PT100: (-100-500)          Cu50: (-50 ~150)

K(-50. 0~150. 0)E(-50. 0~150. 0)J(-50. 0~100. 0)PT100(-50. 0~100. 0)Cu50(-50. 0 ~150. 0)

Input type

KEJ

PT100Cu50

Display Accuracy

0. 1

1

0. 1

1

tolerance

±0. 5%FS

±1%FS

±0. 5%FS

±1%FS

               
Product model

 

FOXB -   1 2 3 4                         

 

SN

Name

Explanation

(1)

Outer Dimension (mm)

A: 48mm×48mm×85mm              B:   48mm×96mm×82mm

C: 96mm×48mm×82mm              D:     72mm×72mm×82mm

E: 96mm×96mm×82mm       

(2)

Power supply type

1: Linear power supply 2: Switching power supply

(3)

OUT1 output type

1:   relay  contact  switch  output(customize NO contact ) 2:   logic  level  output  (used  to  control  SSR) 3:   single-phase  SCR  zero-crossing  trigger  output(to control thyristor) 

4:   4~20mA output          5: 0~5V output      6: 0~10V output         

7: phase-shift trigger SCR        8: 0~10mA output

 

(4)

OUT2/ALM output type

0: No output  1:   relay  contact  switch  output 2:   logic  level  output  (used  to  control  SSR) 

Specification code: -  1    2    3      4  5                                                                                                                                                                   

 

SN

Name

Explanation

(1)

OUT1 control methods

1: PID auto-tuning and fuzzy control    2: Step control

(2)

OUT2/ALM control methods

0: no alarm      1: upper limit alarm           2: lower limit alarm    3: lower/upper limit alarm   4: lower limit upward alarm  5: lower limit downward alarm (keep)

(3)

Input type

1: K        2: E        3: J        4: Pt100        5: Cu50

 

(4)

Upper limit of measuring range

1: 100          2: 150          3: 400      4: 600

5: 800          6: 1000        7: 1200

(5)

Display accuracy

0: 1                1: 0. 1