Product Main

Specifications

The  partial  discharge  detector  is  widely  used  to  test  partial  discharfe  of  motors,   transformers,   cables,   casing,   power  capacitors,   high  voltage  switch,   zinc  oxide  lightning  arrester  and  other  high-voltage  electrical  appliances.
 
Features:  
 
1.   large  scale  integrated  circuit  make  the  tester  more  stable  and  accurate..  
2.   large-screen  CRT,   the  screen  area  to  work  effectively  100  ×   80mm,   can  be  clearly  observed  discharge  waveform.  
3.   with  A,   B,   C  three-channel  test  interface,   more  convenient  testing.  
4.   using  double-header  shows  the  amount  of  discharge,   both  figures  table  shows  PC  value,   while  another  pointer  header  shows  PC  value,   the  pointer  table  can  be  divided  into  linear  and  logarithmic  instructions.  
5.   Low  noise,   high  detection  sensitivity,   wide  capacitance  coverage  area 
6.   Small  size  and  light  weight  make  it  easy  to  carry.
 
 
Main  technical  index:  
 
1.   Testing  scope:   6PF  -  250uF
2.   Sensitivity:   0. 02PC
3.   Amplifier  band:  
      (1)  low-end:   10KHZ,   20KHZ,   40KHZ  optional 
      (2)  high-end:   80KHZ,   200KHZ,   300KHZ  optional 
4.   Amplifier  adjustment:  
6  coarse  grade,   20db  each  grade;  
scope  of  fine-tune>   20db.  
5.   Time  window:  
      (1)  Window  Width:   15  -  150° Adjustable   
      (2)  Window  Position:   Each  window  can  be  rotated  0  -170°  
      (3)  2  windows  can  be  opened  separately  or  simultaneously.
6.   Discharge  scale:  
      (1)  Analog  Meter:   logarithmic  scale  1-10-100,   error<5% 
            linear  scale  0-1000  Error<5%  (based  on  full-scale  meter) 
      (2)  Digital  Header:   3. 5  LED  shows  0-100,   error<5% 
7.   Elliptical:  
      (1)  Frequency  50HZ,   100HZ,   150HZ,   200HZ,   400HZ 
      (2)  Elliptical  rotation:   30° each  grade,   it  can  be  used  for  120° rotation 
      (3)  Display:   Oval  -  straight  line 
      (4)  high-frequency  input  voltage: 13V-275V,     power: <1VA 
8.   Testing  Voltmeter:  
      (1)  Range:   100KV  (expandable) 
      (2)  Display:   3. 5  digital  voltmeter  instructions 
      (3)  Accuracy:   5% 
9,   Power  supply:   220V