Product Main

Specifications

Water source heat pump unit is a kind of new water-cooled air conditioning units with energy-efficient utilizing renewable energy and pollution-free to use for heating or cooling.It consists of closed compressor, condenser, evaporator, throttling apparatus and other cooling accessories.It is a kind of air conditioning equipment can operate round-the-clock.
System uses surface soil or solar energy stored in water bodies as cold and heat sources, assists with compressor system and consumes partial energy.In winter, low quality heat energy in water is taken out to supply indoor heating and air conditioning.In summer, the indoor heat is taken out and released into the water to achieve the purpose of air conditioning.The operation is stable for water source heat pump and is not affected by outside climate.
Normally, 1kw input power can obtain the cold & heat 4KW above, Energy-saving is over 30% comparing with conventional heat-supplied air conditioning systems.
It's appreciate that if you contact us for more details of our products

Goldsun Water Source Heat Pump
Model 3P GSQ-13 5PGSQ-22 6P GSQ-25 10P GSQ-44 12P GSQ-50 20P GSQ-76 25P GSQ-90
Cooling Capacity KW 11 18 20 36 40 55 80
Heating Capacity KW 13 22 25 44 50 76 90
Hot Water Supply L/h 240 470 530 940 1060 1640 1940
Input Power KW 2.8 4.4 5.2 4.4×2 5.2×2 8.6×2 10.3×2
Rated Current A 12.5/4.8 8.6 9.1 8.6×2 9.1×2 28.8 34.1
Hot Water Flow m3/h 2.5 4.1 5 8 10 15.2 19.3
Heating Source Water Flow m3/h 2.1 3.5 4.2 7 8.4 15.2 19.3
Pipe dia.(mm) DN25 DN25 DN25 DN32 DN32 DN65 DN65
Power Supply V/Hz     220  / 380/50 380/50 380/50 380/50 380/50 380/50 380/50
Rated Temp. (℃) 55 55 55 55 55 55 55
Max. Temp.(℃) 60 60 60 60 60 60 60
Refrigerant R22 R22 R22 R22 R22 R22 R22
Refrigerant Weight(kg)              
Noise bB(A) 40 45 45 48 48 50 52
Net weight Kg 110 135 155 310 350 860 950
Size mm(L×W×H) 800×500×850 800×500×850 800×500×850 1100×760×1150 1100×760×1150 13500×980×1450 13500×980×1450
Above parameters are the testing results under the standard working conditions:  
Standard working conditions:    
- - Environment temperature of machine set: dry-bulb 20℃ ,wet bulb 15℃, inlet water 20℃.
Due to the changes in product design, these parameters may change without notice. All the parameters refer to the parameters of the machine nameplate.