Product Main

Specifications

WL-AQD-A01 is especially used to detect indoor air quality. It can detect the level of CO2, temperature, humidity and VOC, which is helpful to control related devices and ensure excellent living condition
   
Main Features
Detect indoor air parameters including CO2, temperature & humidity and VOC
 Compact appearance and reasonable price
 Automatically control devices such as AC.
Production Description
It can be also mounted in the existed or being installed ventilation system to reduce the installation cost.
 WL-AQD-01 integrates 4 sensors which can measure the level of CO2, temperature, humidity and VOC indoor at the same time. The air quality changes at any point indoor will be detected and the data collected will be transferred through RS485 and RS232 interface to realize the function of intelligent control of AC, humidifier and other ventilations etc.
 
Main Parameters
 
Working parameters
Working temperature
0 ~ 50℃
Working humidity
0 ~ 95%RH
Store temperature
-20 ~ 60℃
Powersupply input
DC 12V
Current consumption
Average value is 50mA,peak value is 600mA
Signal output
RS-485, RS-232 (TX only)
Size
75W x 120H x 22D (mm)
CO2 test
Test method
NDIR
Measurement range
0~2,000ppm / 0~5,000ppm / 0~10,000ppm(optional )
Test precision
±30ppm±5% indication(0 ~ 50℃)
Sampling time
3 secs
Response time(90%)
≤ 30 secs
Temperature measurement
Measurement range
-20 ~ 60℃
Precision
±1℃
Humidity measurement
Measurement range
0 ~ 95%RH
Precision
±5%RH
VOC measurement
Test gas
TVOC, HC etc
Test method
Semiconductor technology