Product Main

Specifications

Diesel Genset UK Perkins Series:

Specification:

MAIN SPECIFICATION OF GENERATOR SETS POWERED BY UK Perkins
GENSET MODEL GF-PE584 GF-PE640 GF-PE720
Continuous output (Kw/Kva) 584/730 640/800 720/900
Standby output (Kw/Kva) 642.4/803 704/880 792/990
TECHNICAL DATA
DIESEL ENGINE MODEL 4006-23TAG2A 4006-23TAG3A 4008TAG1A
Prime Power (Kw) 620 679 762
Standby Power (Kw) 697.5 746.9 857.3
Cylinder Number 6 6 8
Cylinder arrangement Vertical in-line Vertical in-line Vertical in-line
Cycle 4 stroke 4 stroke 4 stroke
Induction system Turbocharged and air-to-air charge cooled
Bore (mm) 160 160 160
Stroke (mm) 190 190 190
Combustion system Direct injection
Cooling system Water-cooled
Displacement (litres) 22.921 22.921 30.561
Compression ratio 13.6:1
Direction of rotation Anti-clockwise viewed on fly wheel
Firing order 1,5,3,6,2,4
Total lubrication system capacity(litre) 113.4 113.4 153
Total coolant capacity (litre) 105 105 143
Alternator Model SWA404A SWA404G SWA404H
Continuous output (Kw/Kva) 584/730 640/800 720/900
Power efficiency 94.90% 93.40% 93.50%
Characters 4 Pole, Rotating Field, Brushless, Self excited, H class insulation, IP21,AVR440,12 Winding leads
Voltage regulation ±1.0% with 4% engine governing
Waveform distortion No load∠1.5% and non-distorting balanced linear load ∠5%
THF/TIF ∠2%/∠50