Diesel Genset UK Perkins Series:
Specification:
Specification:
| MAIN SPECIFICATION OF GENERATOR SETS POWERED BY UK Perkins | |||||||
| GENSET MODEL | GF-PE584 | GF-PE640 | GF-PE720 | ||||
| Continuous output (Kw/Kva) | 584/730 | 640/800 | 720/900 | ||||
| Standby output (Kw/Kva) | 642.4/803 | 704/880 | 792/990 | ||||
| TECHNICAL DATA | |||||||
| DIESEL ENGINE MODEL | 4006-23TAG2A | 4006-23TAG3A | 4008TAG1A | ||||
| Prime Power (Kw) | 620 | 679 | 762 | ||||
| Standby Power (Kw) | 697.5 | 746.9 | 857.3 | ||||
| Cylinder Number | 6 | 6 | 8 | ||||
| Cylinder arrangement | Vertical in-line | Vertical in-line | Vertical in-line | ||||
| Cycle | 4 stroke | 4 stroke | 4 stroke | ||||
| Induction system | Turbocharged and air-to-air charge cooled | ||||||
| Bore (mm) | 160 | 160 | 160 | ||||
| Stroke (mm) | 190 | 190 | 190 | ||||
| Combustion system | Direct injection | ||||||
| Cooling system | Water-cooled | ||||||
| Displacement (litres) | 22.921 | 22.921 | 30.561 | ||||
| Compression ratio | 13.6:1 | ||||||
| Direction of rotation | Anti-clockwise viewed on fly wheel | ||||||
| Firing order | 1,5,3,6,2,4 | ||||||
| Total lubrication system capacity(litre) | 113.4 | 113.4 | 153 | ||||
| Total coolant capacity (litre) | 105 | 105 | 143 | ||||
| Alternator Model | SWA404A | SWA404G | SWA404H | ||||
| Continuous output (Kw/Kva) | 584/730 | 640/800 | 720/900 | ||||
| Power efficiency | 94.90% | 93.40% | 93.50% | ||||
| Characters | 4 Pole, Rotating Field, Brushless, Self excited, H class insulation, IP21,AVR440,12 Winding leads | ||||||
| Voltage regulation | ±1.0% with 4% engine governing | ||||||
| Waveform distortion | No load∠1.5% and non-distorting balanced linear load ∠5% | ||||||
| THF/TIF | ∠2%/∠50 | ||||||