Ca. No Rated Voltage
 (kV)
Rated mechanical load (kN) Section Length (mm) Insulating distance (mm) Min. Nominal creepage distance
(mm)
Diameter of shed (mm) 1min power frequency wet withstand voltage
(kV)
Full wave lightning impulse withstand voltage (peak value)
(kV)
DS-12/70 12 70 330 150 355 88 45 105
DS-15/70 15 70 380 203 460 88 65 140
DS-24/70 24 70 455 260 680 100 70 155
DS-36/70 36 70 519 333 820 98 80 210