Product Main

Specifications

BOT150 DIESEL GEN-SET
TECHNICAL SPCIFICATIONS
BOT 150 kva cummins diesel generator adopted Cummins engine,STAMFORD Alternator and the world famous brand controlling system,which has high quality and fit the standard system of GB/T2819,GB/T2820.
 
150 kva cummins diesel generator SPECIFICATIONS
1.SPECIFICATIONS OF GEN-SET
1.1
SET MODEL
BOT150
1.2
Prime at 50HZ,40℃ ambient
120KW 150KVA
1.3
Standby at 50HZ, 40℃ ambient
130KW 162KVA
1.4
Rated Gen-set output
230/400V 50HZ
1.5
Rated Relative humidity
≤ 60%
1.6
Dimension(L×W×H)
2300×1000×1480mm
1.7
Weight
1580kg
1.8
Fuel consumption 100% prime load
32.4L/h
1.9
Total head radiated to ambient
41KW
1.10
Structure of Gen-set
The Gen-set adopt integrative structure,engine is fix on high strength steel basic frame,anti vibration instrument between the engine and basic frame,cooling fan have protecting cap,control cabinet and circuit breaker installed on Gen-set
1.11
Control system (Optional)
Basic control panel or Advanced control panel with automatically start-up function and other function
2.SPECIFICATIONS OF ENGINE
2.1
Engine Brand
Cummins
2.2
Engine Model
6CTA8.3-G2
2.3
Governor/Class
Electrical
2.4
Cylinder NO.
6
2.5
Engine build
Line
2.6
Fuel spray pattern
PT direct injection
2.7
Start-up method
24V, electric
2.8
Aspiration
Turbocharged/Aftercooled
2.9
Cooling mode
Radiator cooled (enclose water)
2.10
Bore and stroke
114×135 mm
2.11
Compression ratio
16.5:1
2.12
Displacement
8.3L
2.13
Engine Prime Power at 1500rpm
122KWm
2.14
Engine standby power at 1500rpm
133KWm
2.15
Battery capacity
120A/hr
2.16
Starting/Min temperature
4℃
2.17
Lubrication oil capacity
24L
2.18
Coolant capacity – radiator and engine (40℃)
31L
2.19
Exhaust temp – full load prime
540℃
2.20
Exhaust gas flow – full load prime
1785m 3/h
2.21
Exhaust gas back pressure max
75mm Hg
2.22
Air flow – radiator (40℃ ambient)
3.1 m 3/s
2.23
Pusher fan head (duct allowance)40℃
13mmH 2O
2.24
Air intake – engine – full load prime
637.2m 3/h
2.25
Standard Air intake temp
25℃
2.26
Fuel type
#0 Diesel (Natural temperature)
2.27
Filter system
Adopt whole changeable lubricating oil,fuel filter and air filter
2.28
Exhaust system
Adopt industrial high efficiency muffler and ripple pipe
3.SPECIFICATIONS OF ALTENATOR
3.1
Alternator Model
Stamford/UCI274F
3.2
Alternator Type
A.C. Synchronous
3.3
Rated Voltage
230/400V
3.4
Rated Frequency
50HZ
3.5
Rated speed
1500RPM
3.6
Voltage regulation mode
Auto
3.7
Alternator voltage regulation
±5%
3.8
Exciting mode
Brushless self exciting
3.9
Power factor
0.8 (lagging)
3.10
Phase & Threads
three phase four threads
3.11
Rated currency
230.9A
3.12
Efficiency
0.923
3.13
Insulation class
H
3.14
Protection class
IP23
3.15
Single load step to NFPA110
100%
3.16
Standards
IEC34-1
3.17
Max.Ambient Temperature
40℃
3.18
Min Ambient Temperature
-20℃
3.19
Max.altitude
1000m
3.20
Weight
500kg