Product Overview
Applied with advanced MCU single-chip micro-processor, Surface Mount Technology and Two-wire non-polarity Input, the Output Module OM511 possesses 2 kinds of encoding methods both auto-encoding of the Control Panel and electro-encoding of the Address Encoder. It also has the function of auto-measuring Voltage between both ends of the module. This module is used together with the Intelligent Fire Alarm Control Panel OZH4800. The auto-encoding method can take reference to the Instruction of the Control Panel. And the electro-encoding method can take reference to the Instruction of the electronic encoder.
The OM511 Output Module receives the programmed commands from the Control Panel and controls 1 group of the Output signals: NO or NC signal, in order to start the field linkage equipments. Then it receives Feedback signal sent by the linkage equipment after action and transmits the signal of Started and Feedback back to the Control Panel showing the location of the signal, meanwhile lighting the LED indicator. (Blinking green at normal state and Blinking red continuously when Start and Feedback)
Specifications
Supply Voltage: Two-wire bus, DC20V~DC28V, non-polarity; External power, DC24V
Consuming Current of Relay Starting: < 15mA
Standby Current of Bus: < 0.3mA Alarm Current of Bus: < 0.6mA
Capacity of the Relay Contact: DC24V, 1A Range of the address: 1~192
Size: 96×65×37mm (length × width × height)
Using Environment: Temperature: 10°C~+50°C Related Humidity: ≤95% (40±2°C)