Product Main

Specifications

1.    Application
JRS4-d series of Thermal Overload Relay is used in AC circuit 50/60 Hz, rated operational voltage up to AC 660V, for the purpose of the overload protection and phase-failure protection of the motor.
Structure: bimetallic strip
Standard: IEC60947-4, UL508, EN60947-4
With temperature compensation and phase-failure protection function
Auxiliary contacts: NO+NC
Character of service: Uninterrupted duty/ Eight-hour duty/ Intermittent duty
Minimum load for auxiliary circuit: 24V 10mA
2. Working condition and installation condition
 Ambient temperature: -5 to +40℃, and the average temperature in a 24 hour period can not exceed +35℃.
 Humidity is up to 50% at +40℃ ambient temperature, and 90% at 20℃.
 Site altitude: ≤2000m
 Pollution degree: 3
 IP code: IP10
 Installation category: 3
 Installation: Relay shall be installed with screws or mounted on 35mm/75mm DIN rail or Plug-in mounting on Contactors. 
3.USING notice
Thermal relay is qualified before out of the factory, users may not open the cover to mobilize action device, and should follow below points:
 Thermal relay normal work location is the cover of body upward, in the level position.
 Select thermal relay: should attention factors motor’s type, capacity, work condition, start-up and load, then select compatible thermal relays with protected motor according rated current, and should adjust current-conditioning for making compatible to setting current value of thermal relay and rated current value of motor.
 Reset button should on manual reset position when thermal relay out of factory;
When combine thermal relay and contactor, should make the screws tighten, otherwise it may affect characteristics of the relay, or may be subject to vibration off.
JRS4-140d combined by thermal relay body and wiring blocks, not only can installation combined with GSC1-115-170 contactor, but also with GSC1-80-95 contactor, or installation independently, before order, please following below ways to operate matching type:
 Combine with GSC1-115-170 contactor, need thermal relay body and plug block;
Combine with GSC1-80~95 contactor or the contactor of this type, only need thermal relay body.
Combine with CJX4-F range contactor (only can connect by independent way) or installation independently, needs thermal relay body and JRS4-40/80d independently installation plug.
4.Order noticeNeed remark thermal relay’s type, installation way, current adjust area and order volume.Humid hot tropic product remark “TH”, marine product remark “C”;
Example: JRS4-09305d/c10sets
Example: JRS4-09~25d  installation block, 10 sets
Discrete installation block need separate ordered, must specify discrete installation block’s name, type and order volume.