The DXG-40.5(Z) GIS is suitable for power plant, substation, combined substation
and electric power system, which is three phase indoor AC single busbar and
sectioning single busbar with 50Hz, 35kV rated voltage, used to control, accept
and distribute electric power.
Service ambient condition:
Air temperature: Max: +40, Min: -25 (average is not more than 35 in 24 hours)
Altitude above sea level: <= 3000m
Air humidity: The average relative humidity measured in 24 hours is not more than 95%, the average relative humidity per month is not more than 90%, average water vapor pressure measured in 24 hours is not more than 2.2kPa, average water vapor pressure per month is not more than 1.8 kPa.
Without frequent heavy vibration
The range of induction electromagnetic interference of secondary system is not more than 1.6kV
Conditions excluded from above are in need of negotiating with the manufacturer.
Technical Data
Service ambient condition:
Air temperature: Max: +40, Min: -25 (average is not more than 35 in 24 hours)
Altitude above sea level: <= 3000m
Air humidity: The average relative humidity measured in 24 hours is not more than 95%, the average relative humidity per month is not more than 90%, average water vapor pressure measured in 24 hours is not more than 2.2kPa, average water vapor pressure per month is not more than 1.8 kPa.
Without frequent heavy vibration
The range of induction electromagnetic interference of secondary system is not more than 1.6kV
Conditions excluded from above are in need of negotiating with the manufacturer.
Technical Data
Rated voltage | 40.5kV |
Rated frequency | 50,60Hz |
Rated current | 630, 1250, 2000,2500A |
Rated short circuit breaking current | 25, 31.5,40kA |
Rated making current | 50, 63, 80kA |
I min power frequency withstand voltage | 95kV ( phase to phase, phase to earth) |
|
118kV (betwwen isolating clearnace) |
Rated lightning impulse withstand voltage | 185kV ( phase to phase, phase to earth) |
|
215kV (betwwen isolating clearnace) |
Protection degree |
IP67( gas-filled compartment) IP4X (LV compartment) |
Power frequency withstand voltage of auxiliary control circuit (1 min) | 2000V |
Rated short time withstand current | 20kA/4s 25kA/4s, 31.5kA/4s |
Rated peak withstand current |
50,63,80kA |
Every phase main return circuit resistance | <25uΩ |
Rated SF6 gas pressure (20℃) | 0.05Mpa |
Min SF6 gas pressure (20℃) | 0.03Mpa |
Annual SF6 gas loss rate |
<0.5% |
Rated voltage of auxiliary control circuit | DC110/220 |
Dimension (WxDxH) | 600x1400x2550mm |
|
800x1600x2550mm |