Product Main

Specifications

Insulated Power Transformer
11Insulated Power Transformer uses high-quality silicon steel core and laminated by steps. It is advantageous in low loss; low noise, low voltage partial discharge and high anti short-circuit capacity. Now it is widely used in power station, power plant, and gets high praise from them. In 1997, SFSZ9-31500/110 on-load voltage-regulated transformer has passed the test by ministry of mechanical industry.
 
Main functions and characters:
1• Bell type tank and the wave form shell; Increase the strength of oil box, beautiful appearance;
2• Core is with D shape yoke, 45 angle seaming;
3• Core and oil box are well fixed and well protected on moving;
4• Reasonable Winding design in the use of interior and exterior supporting structure of coil; hard paper bucket between coils increases the capacity of anti-shortcut;
5• Advanced assembling method such as cold pressing and welding technology, install coil sets of group process technology, hard paper bucket processing technology.
 
6300-63000/110 series three phase duplex winding non-magnetization regulating distribution transformer
 
Ratedpower
(kVA)
Voltage
Connection
9 loss(KW)
10 loss(KW)
11 loss(KW)
No-load Current (%)
Impedance
Voltage(%)
Weight(t)
Outline Dimension(mm)
Gauge
(mm)
H.V(kV)
L.V(kV)
No-Load Loss
Load Loss
No-Load Loss
Load Loss
No-Load Loss
Load Loss
Oil weight
Transport weight
Total weight
L
B
H
6300
110
121
±2×
2.5%
6.3
6.6
10.5
11
YNd11
9.3
36
8.4
34.2
7.4
34.2
0.77
10.5
4.7
14
18
3900
3300
4150
1475
8000
11.2
45
10.1
40.5
9
40.5
0.77
5
14.4
18.9
4000
3400
4250
1475
10000
13.2
53
11.9
47.7
10.6
47.7
0.72
5.1
16.6
21.5
4200
3500
4420
1475
12500
15.6
63
14
59.9
12.5
59.9
0.71
5.7
19
24.5
4300
3500
4540
1475
16000
18.8
77
16.9
73.2
15
73.2
0.67
6.3
21.6
28.2
4400
3600
4550
1475
20000
22
93
19.8
88.4
17.6
88.4
0.67
6.7
24.2
29
4550
3600
4600
2040
25000
26
110
23.4
104.5
20.8
104.5
0.62
7
29
37.5
5150
3900
4720
2040
31500
30.8
133
27.7
126.4
24.6
126.4
0.60
7.7
33.6
42.2
5200
3900
4900
2040
40000
36.8
156
33.1
148.2
29.4
148.2
0.56
9
39
49.6
5250
4150
5000
2040
50000
44
194
39.6
184.3
35.2
184.3
0.52
15.5
55
73
6500
4200
5000
2040
63000
52
234
46.8
222.3
41.6
222.3
0.48
20
65
81
6800
4400
5100
2040
 
 6300-63000/110 series three phase duplex winding regulating transformer with load
 
Ratedpower
(kVA)
Voltage
Connection
9 loss(KW)
10 loss(KW)
11 loss(KW)
No-load Current (%)
Impedance Voltage (%)
Weight(t)
Outline Dimension(mm)
Gauge
(mm)
H.V(KV)
L.V(KV)
No-Load Loss
Load Loss
No-Load Loss
Load Loss
No-Load Loss
Load Loss
Oil weight
Transport
weight
Total weight
L
B
H
6300
110
121
±8×
1.25%
6.3
6.6
10.5
11
YNd11
10
36
9
34.2
8
34.2
0.80
10.5
6.3
17
20.5
5200
2850
4150
1475
8000
12
45
10.8
42.8
9.6
42.8
0.80
6.6
17.4
22
5250
2900
4200
1475
10000
14.2
53
12.8
50.4
11.4
50.4
0.74
6.9
19.5
24.9
5300
3000
4300
1475
12500
16.8
63
15.1
59.9
13.4
59.9
0.74
7.2
22.5
29.3
5500
3300
4400
2040
16000
20.2
77
18.2
73.2
16.2
73.2
0.69
7.4
24.3
31.3
5550
3400
4500
2040
20000
24
93
21.6
88.4
19.2
88.4
0.69
7.6
27.1
34.6
5600
3600
4550
2040
25000
28.4
110
25.6
104.5
22.7
104.5
0.64
7.8
30.2
38.6
5760
3700
4600
2040
31500
33.8
133
30.4
126.4
27
126.4
0.64
8.6
35
43.5
5900
3800
4700
2040
40000
40.4
156
36.4
148.2
32.3
148.2
0.58
10.8
42.7
50.4
6250
3900
4800
2040
50000
47.8
194
43
184.3
38.2
184.3
0.58
14.4
52.7
65.3
6350
4100
4900
2040
63000
56.8
234
51.1
222.3
45.4
222.3
0.52
18.5
63
76
6550
4300
5000
2040
 
 6300-63000/110 series three phase duplex winding regulating transformer with load
 
Ratedpower
(KVA)
Voltage
Connection
9 loss(KW)
10 loss(KW)
11 loss(KW)
No-load Current (%)
Impedance Voltage (%)
Weight(t)
Outline Dimension(mm)
Gauge
(mm)
H.V(KV)
M.V(KV)
L.V(KV)
No-Load Loss
Load Loss
No-Load Loss
Load Loss
No-Load Loss
Load Loss
Oil weight
Transport
weight
Total weight
L
B
H
6300
110
121
±8×
1.25%
35
38.5
6.3
6.6
10.5
11
YNyn
0d11
12
47
10.8
44.7
9.6
44.7
0.95
H-M:
10.5
H-L:
17-18
M-L:
6.5
6.5
18
22
5500
3000
4400
1475
8000
14.4
56
13
53.2
11.5
53.2
0.95
7.5
21
26
5600
3200
4500
1475
10000
17.1
66
15.4
62.7
13.7
62.7
0.89
8.5
25
29
5700
3400
4550
1475
12500
20.2
78
18.2
74.1
16.2
74.1
0.89
9
26.5
32
6000
3450
4600
2040
16000
24.2
95
21.8
90.3
19.4
90.3
0.84
9.3
28.5
34
6100
3500
4650
2040
20000
28.6
112
25.7
106.4
22.9
106.4
0.84
9.5
31.7
35
6150
3550
4700
2040
25000
33.8
133
30.4
126.4
27.0
126.4
0.78
9.7
35
38.5
6200
3600
4750
2040
31500
40.2
157
36.2
149.2
32.2
149.2
0.78
10
38.6
48
6250
3650
4800
2040
40000
48.2
189
43.4
179.6
38.6
179.6
0.73
11
45
58
6300
3700
4850
2040
50000
56.9
225
51.2
213.8
45.5
213.8
0.73
12
50
63
6400
3800
4900
2040
63000
67.7
270
60.9
256.5
54.2
256.5
0.67
13
54
69
6500
3900
5000
2040
 
6300-63000/110 series three phase non-magnetization regulating transformer
 
Ratedpower
(KVA)
Voltage
Connection
9 loss(KW)
10 loss(KW)
11 loss(KW)
No-load Current (%)
Impedance Voltage (%)
Weight(t)
Outline Dimension(mm)
Gauge
(mm)
H.V(KV)
M.V(KV)
L.V(KV)
No-Load Loss
Load Loss
No-Load Loss
Load Loss
No-Load Loss
Load Loss
Oil weight
Transport
weight
Total weight
L
B
H
6300
110
121
±2
×2.5%
35
38.5
6.3
6.6
10.5
11
YNyn
0d11
11.2
47
10.1
44.7
9
44.7
0.82
step up
H-M:
17-18
H-L:
10.5
M-L:
6.5
step-down
H-M:
10.5
H-L:
17-18
M-L:
6.5
6
17
20
5400
2900
4300
1475
8000
13.3
56
12.0
53.2
10.6
53.2
0.78
7
20
24
5500
3100
4400
1475
10000
15.8
66
14.2
62.7
12.6
62.7
0.74
8
23.5
27
5600
3300
4450
1475
12500
18.4
78
16.6
74.1
14.7
74.1
0.70
8.5
25
30
5900
3350
4500
2040
16000
22.4
95
20.2
90.3
17.9
90.3
0.66
8.8
27
32
6000
3400
4550
2040
20000
26.4
112
23.8
106.4
21.1
106.4
0.65
9
30.5
33
6050
3450
4600
2040
25000
30.8
133
27.7
126.4
24.6
126.4
0.60
9.2
34
36
6100
3500
4650
2040
31500
36.8
157
33.1
149.2
29.4
149.2
0.60
9.5
37.5
46
6150
3550
4700
2040
40000
43.6
189
39.2
179.6
34.9
179.6
0.55
10.5
44
56
6200
3600
4750
2040
50000
52.0
225
46.8
213.8
41.6
213.8
0.55
15.5
55
73
6500
4200
5000
2040
63000
61.6
270
55.4
256.5
49.3
256.5
0.50
20
65
81
6800
4400
5100
2040