Product Main

Specifications

fuse cutout
Drop out fuse and pull loads falling type fuse protection for outdoor HV electrical appliances, installed in the high-voltage side of distribution transformer or distribution lines branch trunk road,used as a transformer and line short-circuit,overload, and points.Drop out fuse holder and fuse from the insulating tube 2 parts. static contact bracket installed in the insulation at both ends,moving contact is installed on both ends of fuse tube, fuse tube from the inner arc tube and the outer phenolic aldehyde paper tube or epoxy glass cloth in to the pipeline. pull load drop fuse increase of auxiliary contact and interrupter over for the points combined load current.
Type Rated 
voltage
(KV)
Operating 
Voltage
(KV)
Rated 
current
(A)
Breaking 
current(KA)
Power 
frequency 
withstand 
voltage(wet)
KV
Power 
frequency 
withstand 
voltage(dry)
KV
Impulse 
voltage
KV
Leakage
distance
(MM)
RW3-10/100 10 11.5 100 6.3 42 30 75 230
RW3-10/200 10 11.5 200 8.0  42 30 75 230
HRW3-10/100 10 11.5 100 6.3 42 30 75 360
HRW3-10/200 10 11.5 200 8.0  42 30 75 360
RW7-10/100 10 11.5 100 6.3 42 30 75 260
RW7-10/200 10 11.5 200 8.0  42 30 75 260
HRW7-10/100 10 11.5 100 6.3 42 30 75 340
HRW7-10/200 10 11.5 200 8.0  42 30 75 340
RW10-10/100 10 11.5 100 6.3 42 30 75 260
RW10-10/200 10 11.5 200 8.0  42 30 75 260
HRW10-10/100 10 11.5 100 6.3 42 30 75 340
HRW10-10/200 10 11.5 200 8.0  42 30 75 340
RW11-10/100 10 11.5 100 6.3 42 30 75 260
RW11-10/200 10 11.5 200 8.0  42 30 75 260
HRW11-10/100 10 11.5 100 6.3 42 30 75 340
HRW11-10/200 10 11.5 200 8.0  42 30 75 340
RW12-10/100 10 11.5 100 6.3 42 30 75 300
RW12-10/200 10 11.5 200 8.0  42 30 75 300
HRW12-10/100 10 11.5 100 6.3 42 30 75 380
HRW12-10/200 10 11.5 200 8.0  42 30 75 380
PRWG1-10/100 10 11.5 100 6.3 50 35 85 315
PRWG1-10/200 10 11.5 200 8.0  50 35 85 315
HPRWG1-10/100 10 11.5 100 6.3 50 35 85 380
HPRWG1-10/200 10 11.5 200 8.0  50 35 85 380
RW10-10F/100 10 11.5 100 6.3 42 30 75 260
RW10-10F/200 10 11.5 200 8.0  42 30 75 260
HRW10-10F/100 10 11.5 100 6.3 42 30 75 340
HRW10-10F/200 10 11.5 200 8.0  42 30 75 340
RW11-10F/100 10 11.5 100 6.3 42 30 75 260
RW11-10F/200 10 11.5 200 8.0  42 30 75 260
HRW11-10F/100 10 11.5 100 6.3 42 30 75 340
HRW11-10F/200 10 11.5 200 8.0  42 30 75 340
PRWG1-10F/100 10 11.5 100 6.3 50 35 85 315
PRWG1-10F/200 10 11.5 200 8.0  50 35 85 315
HPRWG1-10F/100 10 11.5 100 6.3 50 35 85 380
HPRWG1-10F/200 10 11.5 200 8.0  50 35 85 380
PRWG2-35/100 35 40.5 100 5.0  95 86 185 935
PRWG2-35/200 35 40.5 200 8.0  95 86 185 935
HPRWG2-35/100 35 40.5 100 5.0  95 86 185 1340
HPRWG2-35/200 35 40.5 200 8.0  95 86 185 1340
RW5-35/100 35 40.5 100 5.0  95 86 185 746
RW5-35/200 35 40.5 200 8.0  95 86 185 746
HRW5-35/100 35 40.5 100 5.0  95 86 185 1080
HRW5-35/200 35 40.5 200 8.0  95 86 185 1080
Type Rated 
voltage
KV
Rated 
current
A
Breaking 
current
A
Impulse 
voltage
BIL
Power 
frequency 
withstand 
voltage
KV
Leakage 
distance(MM)
Weight(KG) Dimensions(CM)
GD-1 12 100 10000 110 40 245 7 41*39*11.5
GD-1 12 200 12000 110 40 245 7.5
GD-2 15 100 10000 125 45 330 9 51*34*12.5
GD-2 15 200 12000 125 45 330 9.5
GD-3 24 100 8000 150 65 420 11.5 52*38*13
GD-3 24 200 10000 150 65 420 12
GD-4 27 100 8000 150 65 450 11.5 52*38*13
GD-4 27 200 10000 150 65 450 12
GD-5 33 100 10000 170 70 660 14.5 66*37*14
GD-5 33 200 12000 170 70 660 15
GD-6 33 100 10000 170 70 660 7 61*42*13
GD-6 33 200 12000 170 70 660 7.5
GD-7 24 100 8000 150 65 370 11 52*38*10.5
GD-7 24 200 10000 150 65 370 11.5
GD-8 33 100 10000 170 70 700 15.5 57*38*14.5
GD-8 33 200 12000 170 71 700 16
GD-9 11 100 6000 110 42 340 7 47.5*27.5*11.5
GD-9 11 200 8000 110 42 340 7.5
GD-10 11 100 6000 110 42 340 5 47.5*27.5*11.5
GD-10 11 200 8000 110 42 340 5.5
GD-11 33 100 8000 10 70 780 23 69*28*18
GD-11 33 200 10000 170 70 780 23