Product Main

Specifications

Product Description
General:
S11-M. R Three Phase Enclosed Distribution Transformer with wound-core is applicable to 10kV, 6kV transmission and distribution system for distribution, power supply and lighting in industrial, agricultural, mineral and petrochemical fields. Compared with series S9, 30% of no-load loss and 70% of no-load current can be decreased averagely. It is remarkable in saving energy. In addition to, its noise level is in conformity to national environmental protection policy. Therefore, it is regarded as wonderful product both in energy saving and environmental protection.
Service condition:
Normal service condition:
Elevation height less than 1000m
Environmental temperature
Max. Temperature +40 oC
Max. Daily average temperature: +30 oC
Max. Annual average temperature +20 oC
Min. Temperature -30 oC
Operation environment outdoor
Symmetry of multi-phase power source
Feature:
Core is wound by silicon strip with lower loss. Enclosed structure is also called as R-shaped core. Core limb and yoke cross-section is close to a circle. It is impact, lower no-load loss and smaller current. Due to fully enclosed transformer, isolation between oil and air keeps insulation away from moisture, which lowers insulation aging and improves service life. The product is free from untanking before operation and is free from maintenance during operation. Owing to the corrugated plate used for cooling for S11-M. R. Series, oil volume is changed by adjustment and compensation through expansion and shrinkage of corrugated plate when the temperature of oil is changed.
Ordering Notes:
1. Rated capacity
2. Phase number
3. Frequency
4. Rated voltage (L. V. &H. V. )
5. Tapping range
6. Vector group
 
 
  Voltage combination and tapping range
 
 
 
 
 
 
  Item  Capacity (kVA)
  H.V. kV
  Tapping range %
L.V. kV
 
  Impedance voltage
(%)
No-load loss (W)
  No-load   current (%)
 On-load losses (W)
 30
  6  6.3 10.5  10 11
  +/-5% +/-2X2.5%
  0.4
  4.0
 90
 0.60
 600
 50
 
 
 
 
 120
 0.60
 870/950
 63
 
 
 
 
 140
 0.57
 1040/1110
 80
 
 
 
 
 175
 0.54
 1250/1360
 100
 
 
 
 
 200
 0.48
 1500/1615
 125
 
 
 
 
 235
 0.45
 1800/1810
 160
 
 
 
 
 280
 0.42
 2200/2380
200
 
 
 
 
335
0.39
 2600/2610
250
 
 
 
 
390
0.36
 3050/3130
315
 
 
 
 
465
0.33
 3650/3750
400
 
 
 
 
560
0.30
 4300/4450
500
 
 
 
 
670
0.30
 5150/5330
630
 
 
 
  4.5
840
0.27
 6200/6510
800
 
 
 
 
1000
0.24
 7500/7880
1000
 
 
 
 
1200
0.24
 10300/10830
1250
 
 
 
 
1400
0.24
 12000/12600
 
 
 
 
  Voltage combination 
and tapping range
 
 
 
 
 
  Item Capacity
(kVA)
  H.V. kV
  Tapping range %
L.V.
kV
Impedance voltage (%) 
  Track Gauge
(mm)
  Outline dimension (mm) LxWxH (axbxc)
 30
  66  6.3 10.5 10 11
  +/- 5%
 +/- 2X2.5%
 0.4
 4.0
 400
 800*600*960
 50
 
 
 
 
 
 940*660*1005
 63
 
 
 
 
 
 980*690*1030
 80
 
 
 
 
 
 1020*705*1040
 100
 
 
 
 
 
 1050*720*1070
 125
 
 
 
 
 550
 1080*730*1120
 160
 
 
 
 
 
 1160*760*1165
 200
 
 
 
 
 
 1200*790*1180
 250
 
 
 
 
 
 1370*770*1230
 315
 
 
 
 
 
 1400*780*1310
 400
 
 
 
 
 660
 1470*840*1365
 500
 
 
 
 
 
 1480*810*1425
 630
 
 
 
 4.5
 
 1620*910*1515
 800
 
 
 
 
 820
 1650*930*1560
 1000
 
 
 
 
 
 1750*1030*1630
 1250
 
 
 
 
 
 1805*1055*1755