AVR-15A
Features
<± 0.5% Regulation
220/400 VAC Programmable Input
Rugged Compact Design
With Under Frequency Protection
Soft Start Voltage Ramping
EMI Suppression
Built-in Hihg Capacity 8Amp Fuse
Specifications
Sensing lnput Voltage: 220/400VAC,1 phase 2 wire
Power Input Voltage: 100-240VAC, 1 phase 2 wire
Output Voltage:
Current: Continuous 6A
Intennittent :12A for 10SEE.
Resistance: Min.10 Ohm, Max. 100 Ohm
Voltage Build-up: Residual volts at AVR temina!>5VAC
External Volts Adjustment: ±7%with 1K Ohm Iwatt uimmer
Soft Start Ramp Time: 3sec.
Unit Power Dissipation: Max.8Watt
EMI Suppression: Internal Electromagnetic Interference Filtering
Thermal.Drift: 0.05% per change in AVR ambient
Under Frequency Protection: 60Hz system presets knee point at 57Hz
(Facto'1' Settings): 50Hz system presets knee point at 47Hz
Volts Regulation: <± 0.5%(with 4%engine governing)
Environment
Vibration 3G@ 100-2KHz
Operating Temperatuer -40-65°C
Relative Humidity <95%
Storage Temperature -40-85 °C
We also have GAVR 8A GAVR 12A.