1)to be laid underground,
2)the cable could bear certain mechanical force,
3)but it couldn' bear great pulling force.

 
XLPE Power Cable Standard:
Equivalent IEC 60502-2, GB/T12706.2;
Rated Voltage 6 kV (Um=7.2kV) to 30 kV (Um=36kV) Power Cable.

Operating Features:
1)The maximum conductor operating temperature: 90°C;
During short circuit (lasting less than 5 seconds) the maximum temperature of the cable conductor shall not be above 250°C;
Environment temperature should be no lower than 0°C for laying the cable.
2)Bending Radius of the Cable:
Single Core Cable: Non Armored Cable 20D, Armored Cable 15D;
Cores Cable: Non Armored Cable 15D, Armored Cable 12D.
 
 Table 1, Test Voltage and Maximum Discharge Capacity of the Cable

Rated Voltage (kV)
3.6/6 6.0/6.0 8.7/10 12.0/20 18/30 21/35 26/35
6.0/10 8.7/15
Test Voltage (kV) 6.23 10.38 15.05 20.76 31.14 36.33 44.98
Max.Discharge Capacity (pC) 10 10 10 10 10 10 10
 
 Table 2, AC Voltage Test of Cable

Rated Voltage (kV)
0.6/1 1.8/3 3.6/6 6.0/6 8.7/10 12.0/20 18/30 21/35 26/35
3.6/10 6.0/10 8.7/15
Test Voltage (kV) 3.5 6.5 12.5 21 30.5 42 63 73.5 91
Test Time (min) 5 5 5 5 5 5 5 5